PENSOTTI Solenne PCH50B-H Instruction Manual page 48

Condensing direct vent gas boiler 170,000 btu input
Hide thumbs Also See for Solenne PCH50B-H:
Table of Contents

Advertisement

PARAMETER
TYPE OF OPERATION
Sets the 0-10V industrial bus piloting.
P18
Not applicable to this model.
P19
Central heating minimum set point
P20
Central heating maximum set point
P21
D.H.W maximum set point
∆T set point T° flow / T° return
P22
(w/modulating pump and return
temperature sensor connected only)
Modulating pump minimum speed
P23
(w/modulating pump and return
temperature sensor connected only)
Modulating pump maximum speed
P24
(w/modulating pump and return
temperature sensor connected only)
∆T timing T° flow / T° return
P25
(w/modulating pump and return
temperature sensor connected only)
P26
Outdoor reset function
NOTES:
P04 -
This parameter allows to modify the time the boiler takes (in heating mode) to reach the maximum power set.
P10, P11, P12 -
These parameters are automatically set according to the output value set in Parameter P00.
The maximum boiler power, in heating mode, can be set according to the paragraph 5.5 "Heating output (Kw) –
P13 -
Fan frequency (Hz) diagram".
Professionally qualified
personnel in accordance
with current laws and
standards and in line
with the manufacturer's
instructions must install the
appliance.
REGULATION INSTRUCTIONS
PARAMETER
VALUE
00-02
68 - 104
104 - 194
113 - 167
N/A
N/A
N/A
00
01
FUNCTION
00 = Disabled (default)
Displayed in °F
Displayed in °F
Displayed in °F
32 = Disabled (default)
N/A
N/A
N/A
00 = Standard Operation 86°F – 185°F
01 = Outdoor sensor NOT connected
86 °F – 140°F.
Outdoor sensor IS connected
86°F – 176°F
(default)
45

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pci 18/8-h

Table of Contents