5. REGULATING THE APPLIANCE

5.1 Parameters table

PARAMETER
TYPE OF OPERATION
P00
Selects the model of boiler
Selects the type of boiler
P01
P02
Selects the type of gas supply
Sets the central heating
P03
temperature
P04
Heating output rising time
Water hammer prevention
P05
function
D.H.W priority function.
P06
heat call for 90 seconds after
DHW call)
P07
Central heating timer
Central heating pump overrun
P08
timer
D.H.W/Storage cylinder pump
P09
overrun timer
Minimum fan speed – DHW
P10
P11
Maximum fan speed - DHW
Minimum fan speed –
P12
Heating
Maximum fan speed –
P13
Heating
P14
Sets the ignition sequence
Legionella prevention function
P15
(for storage boilers only)
Outdoor reset curve
P16
(w/outdoor temperature
sensor only installation)
Sets the temperature
P17
measurement unit
REGULATION INSTRUCTIONS
PARAMETER
VALUE
00-06
00-05
00
01
02
00
01
00-04
00
01
(Delays
00
01
00 - 90
00 - 90
00 - 90
38 Hz (Nat Gas)
50 Hz (Propane)
185 Hz (Nat Gas)
183 Hz (Propane)
38 Hz (Nat Gas)
50 Hz (Propane)
145 Hz (Nat Gas)
14 Hz (Propane)
90 Hz (Nat Gas)
110Hz (Propane)
00
01
00-30
00
01
FUNCTION
01 = 18 KW
04 = 34 kW
05 = 50 kW
All other numbers N/A
00 = N/A
01 = PCC 34
02 = PCI 18/8 & PCI 34/20
03 = PCH 18/B, PCH 50/B & PCH 50/B
indirect)
04 = N/A
05 = Only heating boiler
(NO indirect connected.
See 3.6)
00 = Natural gas
01 = LPG
02 = N/A
00 = Standard (95-185°F)
01 = Reduced (77-113°F)
00 = 0 seconds (Disabled)
01 = 50 seconds (Default)
02 = 100 seconds
03 = 200 seconds
04 = 400 seconds
00 = Off (default)
01 = On
00 = Off
01 = On
Displayed in multiples of 5 seconds
(default value 36 x 5 = 180")
Displayed in multiples of 5 seconds
(default value 36 x 5 = 180")
Displayed in multiples of 5 seconds
(default value 18 x 5 = 90")
Displayed in hertz
(1Hz = 30 rpm)
Displayed in hertz
(1Hz = 30 rpm)
Displayed in hertz
(1Hz = 30 rpm)
Displayed in hertz
(1Hz = 30 rpm)
Displayed in hertz
(1Hz = 30 rpm)
00 = Off
01 = On (default)
See the graph in the parameter setting
explanation
00 = °C
01 = °F
(with
44