PARAMETER P08 – CENTRAL HEATING PUMP OVERRUN TIMER
This parameter is used to set the pump functioning time, in heating mode, after switching off the main burner for
the intervention of the room thermostat
(
displayed in multiples of 5 seconds
min = 00
max = 90
For ex.:
90 = 90 x 5 sec = 450 sec (7,5 min)
36 = 180 sec = 3 min
The default value is
PARAMETER P09 – D.H.W/STORAGE CYLINDER PUMP OVERRUN TIMER
This parameter is used to set the pump functioning time, in D.H.W mode, after closing the water tap
(
displayed in multiples of 5 seconds
min = 00
max = 90
For ex.:
90 = 90 x 5 sec = 450 sec (7,5 min)
The default value is
18 = 90 sec = 1.5 min
PARAMETER P10 – SETS THE MINIMUM FAN SPEED
This parameter is used to set the minimum fan speed which corresponds to the minimum burner
output.
(
in Hertz):
displayed
min = 33 Hz
max = Value set in parameter P11
The default value is set according to the output value set in Parameter P00.
PARAMETER P11 – SETS THE MAXIMUM FAN SPEED
This parameter is used to set the maximum fan speed which corresponds to the maximum burner
output.
(
in Hertz):
displayed
min = Value set in parameter P10
max = 203 Hz
The default value is set according to the output value set in Parameter P00.
PARAMETER P12 – SETS THE MINIMUM FAN SPEED (CENTRAL HEATING)
This parameter is used to set the minimum fan speed in heating mode, which corresponds to the
minimum burner output during a heating mode request.
(
in Hertz):
displayed
min = 33 Hz
max = Value set in parameter P13
The default value is set according to the output value set in Parameter P00.
PARAMETER P13 – SETS THE MAXIMUM FAN SPEED (CENTRAL HEATING)
This parameter is used to set the maximum fan speed in heating mode, which corresponds to the
maximum burner output during a heating mode request [see paragraph 5.5 Heating output (kW) – Fan
frequency (Hz) diagram].
(
in Hertz):
displayed
min = Value set in parameter P12
max = 203 Hz
The default value is set according to the output value set in Parameter P00.
PARAMETER P14 – SETS THE IGNITION SEQUENCE
This parameter is used to set the fan speed during the starting up of the boiler.
(displayed in Hertz):
min = Value set in parameter P10
max = 203 Hz
The default value is set according to the output value set in Parameter P00.
MAINTENANCE INSTRUCTIONS
.
):
):
.