PARAMETER P20 – CENTRAL HEATING MAXIMUM SET POINT
This parameter is used to set the central heating maximum temperature the user may increase to. The
user will be unable to increase the maximum heating temperature above this set number.
min = 104°F
max = 194°F
PARAMETER P21 – D.H.W. MAXIMUM SET POINT
This parameter is used to set the D.H.W maximum temperature the user may increase to. The user
will be unable to increase the maximum D.H.W. temperature above this set number.
min = 113°F
max = 167°F
PARAMETER P22 – ∆T SET POINT T° FLOW / T° RETURN - (not applicable)
Value set to "32" – Do not change. If set to anything other than "32", Error "E15" will appear.
PARAMETER P23 – (not applicable)
PARAMETER P24 – (not applicable)
PARAMETER P25 – (not applicable)
PARAMETER P26 – OUTDOOR RESET FUNCTION
This parameter is used to set the D.H.W maximum temperature the user may increase to.
00 = Standard Operation 86°F – 185°F
01 = Outdoor sensor NOT connected the allowed operating temperature range is 86 °F – 140°F
Outdoor sensor IS connected the allowed operating temperature is 86°F – 176°F
Professionally qualified personnel in accordance with current laws and
standards and in line with the manufacturer's instructions must install the
appliance.