MAINTENANCE INSTRUCTIONS

6. MAINTENANCE (qualified personnel)

6.1 General Warnings

BOILER CLEANING / MAINTENANCE IS REQURIED TO BE PERFORMED ON AN ANNUAL BASIS.
All maintenance operations must be carried out by professionally qualified personnel.
In order to guarantee the long life of the appliance and in accordance with the current gas safety
regulations, only use original replacement parts
Before carrying out any type of maintenance operation, disconnect the appliance from the electrical
supply and shut off the gas valve.
Warranty will not be offered if annual maintenance is not performed.
Keep appliance area clear and free from combustible material, gasoline and other flammable vapors
and liquids.
In order to safeguard all waterside components, the supplied Fernox Commissioning Kit must be
used in its entirety.

6.2 Maintenance

Annual examination of the entire venting system is required.
Make sure all the venting connections/joints are tight and in good condition where visible.
Clean the burner cylinder using a non-metal brush and without damaging the ceramic fiber.
Clean the heat exchanger using a recommended detergent from PENSOTTI for the stainless steel. Do
not wet the ceramic fiber coating.
Visually inspect the burner flame. The flame must burn with a clear blue, stable flame. If the
burner flame appearance is not satisfactory or debris is visible on the burners, remove and clean
with a vacuum cleaner.
Using an electronic combustion analyzer verify the CO2 value in the flue gases is as specified by
Pensotti for the gas being burned.
All electric motors are permanently lubricated and do not need oiling. Remove the combustion air
blower and clean wheel and housing with soft brush or vacuum.
Verify proper operation after any servicing.
Wipe the outside surface with a wet cloth; then dry the surface. Use a neutral detergent to clean any
stains.
Vent termination should be inspected for blockage during maintenance checks.
Check for blockage at the drain pipe and condensate trap.
Clean condensate trap and check for correct level of water.
Check for water leaks from the equipment and piping.
Warranty will not be offered if annual maintenance is not performed.
55