Removing Wires From The Push-In Plus Terminal Block - Omron S8VK-WA Series Manual

Switch mode power supply (240/480-w models)
Hide thumbs Also See for S8VK-WA Series:
Table of Contents

Advertisement

Connecting Stranded Wires
Use the following procedure to connect the wires to the terminal block.
1. Hold a flat-blade screwdriver at an angle and insert it into the
release hole.
The angle should be between 10° and 15°. If the flat-blade
screwdriver is inserted correctly, you will feel the spring in the
release hole.
2. With the flat-blade screwdriver still inserted into the release hole,
insert the wire into the terminal hole until it strikes the terminal
block.
3. Remove the flat-blade screwdriver from the release hole.
10° to 15°
Flat-blade screwdriver
Checking Connections
• After the insertion, pull gently on the wire to make sure that it will
not come off and the wire is securely fastened to the terminal block
• The insulation distance is still satisfied although some of the
conductor may still be visible after being inserted into the terminal
block, even though recommended ferrules are used.
Removing Wires from the Push-In Plus Terminal
Block
Use the following procedure to remove wires from the terminal block.
The same method is used to remove stranded wires, solid wires, and
ferrules.
1. Hold a flat-blade screwdriver at an angle and insert it into the
release hole.
2. With the flat-blade screwdriver still inserted into the release hole,
remove the wire from the terminal insertion hole.
3. Remove the flat-blade screwdriver from the release hole.
10° to 15°
Flat-blade screwdriver
Recommended Ferrules and Crimping Tools
Recommended Ferrules
S8VK-WA@@@24: Input Terminals/PE Terminals
S8VK-WA24024: DC Output Terminals
S8VK-WA@@@24:
(mm
2
3
1
1/1.25
1.25/1.5 17/16
Recommended crimp tool
Note: 1. Make sure that the outer diameter of the wire is smaller than
2
3
1
S8VK-WA48024: DC Output Terminals
(mm
Recommended crimp tool
Note: 1. Make sure that the outer diameter of the wire is smaller than
Signal Output Terminals/COM Terminals
Applicable
Ferrule
Stripping
wire
Condu
length
ctor
(mm)
length
(Ferrules
2
) (AWG)
(mm)
used)
8
10
AI 0, 25-8
0.25
24
10
12
AI 0, 25-10
8
10
AI 0,34-8
0.34
22
10
12
AI 0,34-10
8
10
AI 0,5-8
0.50
20
10
12
AI 0,5-10
8
10
AI 0,75-8
0.75
18
10
12
AI 0,75-10
8
10
AI 1-8
18/17
10
12
AI 1-10
8
10
AI 1,5-8
10
12
AI 1,5-10
2.5
14
10
12
AI 2, 5-10
CRIMPFOX6
CRIMPFOX6T-F
CRIMPFOX10S
the inner diameter of the insulating sleeve of the
recommended ferrule.
2. Make sure that the ferrule processing dimensions conform
to the following figure.
8 to 10 mm
2.8 mm max.
2.6 mm max.
Applicable
Ferrule
Stripping
wire
Conduct
length
or
(mm)
length
(Ferrules
2
) (AWG)
(mm)
used)
4
12
12
14
AI 4-12
6
10
12
16
AI 6-12
CRIMPFOX6
CRIMPFOX6T-F
CRIMPFOX10S
the inner diameter of the insulating sleeve of the
recommended ferrule.
2. Make sure that the ferrule processing dimensions conform
to the following figure.
12 mm
4 mm max.
4 mm max.
S8VK-WA
Recommended Ferrules
Phoenix
Weid
Wago
Contact
muller
H0.25/12
FE-0.25-8N-YE
---
---
H0.34/12
FE-0.34-8N-TQ
---
---
H0.5/14
FE-0.5-8N-WH
H0.5/16
FE-0.5-10N-WH
H0.75/14
FE-0.75-8N-GY
H0.75/16
FE-0.75-10N-GY
H1.0/14
FE-1.0-8N-RD
H1.0/16
FE-1.0-10N-RD
H1.5/14
FE-1.5-8N-BK
H1.5/16
FE-1.5-10N-BK
H2.5/16DS FE-2.5-10N-BU
PZ6 roto
Variocrimp4
Recommended Ferrules
Phoenix
Weid
Wago
Contact
muller
H4.0/20D FE-4.0-12N-GY
FE-6.0-12N-YE *
H6.0/20
Variocrimp4
* Use the
PZ6 roto
Variocrimp16.
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

S8vk-wa24024S8vk-wa48024

Table of Contents