Omron S8VK-WA Series Manual page 3

Switch mode power supply (240/480-w models)
Hide thumbs Also See for S8VK-WA Series:
Table of Contents

Advertisement

Ratings, Characteristics, and Functions
Item
Efficiency *1
Input voltage range *2
Frequency *2
Input current *1
Input con-
ditions
Power factor
Leakage current *3
Inrush current *4
(for a cold start at 25°C)
Rated output current
Power Boost Function
Voltage adjustment range *5
Ripple noise voltage *6
Input variation influence *7
Output
character-
Load variation influence *8
istics
Temperature variation
influence
Startup time *9
Output hold time *9
Overload protection
Overvoltage protection
Series operation
Additional
Parallel operation
functions
INPUT OK Indicator
DC OK Indicator
Iout > 100% Indicator
DC OK Signal Output
Iout > 100% signal output
Withstand voltage
Insulation
Insulation resistance
Ambient operating temperature *10
Storage temperature
Environ-
ment
Ambient operating humidity
Vibration resistance
Shock resistance
MTBF *11
Reliability
Expected life *12
Weight
Construc-
Cooling fan
tion
Degree of protection
Note: For *1 to *12, refer to page 4.
Power rating
Output voltage
Three-phase 200 VAC input
93% typ.
Single-phase 200 VAC input 92% typ.
Three-phase 230 VAC input
93% typ.
Single-phase 230 VAC input 93% typ.
Three-phase/single-phase 170 to 264 VAC, 265 to 300 VAC (1 second)
240 to 350 VDC
50/60 Hz (47 to 63 Hz)
Three-phase 200 VAC input
0.80 A typ.
Single-phase 200 VAC input 1.4 A typ.
Three-phase 230 VAC input
0.70 A typ.
Single-phase 230 VAC input 1.2 A typ.
0.9 min.
Three-phase 200 VAC input
1 mA max.
Three-phase 230 VAC input
1 mA max.
Three-phase 200 VAC input
13 A typ.
Three-phase 230 VAC input
15 A typ.
10 A
15 A
24 to 29.5 V (with V.ADJ)
Three-phase
50 mVp-p max.
200 to 240 VAC input
at 20 MHz of bandwidth
0.5% max.
1.5% max.
200 to 240 VAC input
0.05%/°C max.
Three-phase 200 VAC input
1,000 ms max.
Three-phase 230 VAC input
1,000 ms max.
Three-phase 200 VAC input
35 ms typ.
Three-phase 230 VAC input
35 ms typ.
Yes, automatic reset, intermittent operation type
Refer to Overload Protection on page 5.
Yes, 130% or higher of rated output voltage, power shut off (shut off the input voltage and
turn on the input again),
Refer to Overvoltage Protection on page 5.
Yes (For up to two Power Supplies; external diodes required.)
Yes (For up to two Power Supplies), Refer to Parallel Operation on page 15.
Yes (LED: Green)
Yes (LED: Green)
Yes (LED: Yellow)
Yes (MOS FET relay output 30 VDC max., 50 mA max.)
Yes (MOS FET relay output 30 VDC max., 50 mA max.)
3.0 kVAC for 1 min. (between all input terminals and all output terminals), cutoff current 20 mA
2.0 kVAC for 1 min. (between all input terminals and PE terminals), cutoff current 20 mA
1.0 kVAC for 1 min. (between all output terminals, signal output terminals and PE terminals),
cutoff current 25 mA
0.5 kVAC for 1 min. (between all output terminals and all signal output terminals), cutoff
current 10 mA
100 MΩ min. (between all output terminals, signal output terminals and all input terminals /
PE terminals) at 500 VDC
-40 to 70°C (Derating is required according to the temperature. Refer to Engineering Data
on page 9.) (with no condensation or icing)
-40 to 85°C (with no condensation or icing)
95% max. (Storage humidity: 95% max.)
10 to 55 Hz, maximum 5 G, 0.42 mm single amplitude for 2 h each in X, Y, and Z directions
294 m/s
290,000 hrs typ.
10 years min.
800 g max.
No
IP20 by EN/IEC 60529
240 W
24 V
2
, 3 times each in ±X, ±Y, ±Z directions
S8VK-WA
480 W
24 V
94% typ.
93% typ.
94% typ.
94% typ.
1.6 A typ.
2.6 A typ.
1.4 A typ.
2.3 A typ.
13 A typ.
15 A typ.
20 A
30 A
120 mVp-p max.
at 20 MHz of bandwidth
30 ms typ.
30 ms typ.
230,000 hrs typ.
1050 g max.
3