S8VK-WA
Identification of error locations at the input, product, and load side by the Indicator or Signal Output,
and troubleshooting for the same (Maintenance point indicator)
Error locations at the input, product, and load side can be identified by the INPUT OK, DC OK, Iout > 100% Indicator / Signal Output.
DC OK
INPUT OK
Indicator/Signal
Indicator
Output
: Lit / ON
: Not lit / OFF
Time chart (Operation of the Indicator/Signal Output according to the product status)
ON
Input voltage
OFF
Indicator: Lit
INPUT OK
Indicator: Not lit
>151%
100%
Output current
0%
Indicator: Lit
Signal Output: ON
Iout>100%
Indicator: Not lit
Signal Output: OFF
Rated voltage
Output voltage
0 V
Indicator: Lit
Signal Output: ON
DC OK
Indicator: Not lit
Signal Output: OFF
6
Iout > 100%
Indicator/Signal
Product operating status
Output
Operation is being performed in
excess of the rated output current of
the product.
Overload protection is activated for
the product, and the output voltage
drops.
The product may have failed, or the
overvoltage protection may have
been activated for the product.
No input voltage is being supplied.
Flashing / ON · OFF
---
(Normal)
Change to a product with less load or larger output capacity.
However, the Power Supply can be used as long as the operating
conditions specified in Peak current (P.14) are satisfied.
Make sure the output line and the load are not short-circuited.
If there is no short-circuiting, change to a product with less load or
larger output capacity.
To check for overvoltage protection, turn the input power OFF, and
then turn it ON again after 3 minutes or more has elapsed. If no
output voltage is output, the product may have failed. Replace the
product.
Make sure the circuit breaker connected to the input side has not
tripped, or the fuse connected to the input side has not blown.
Turn ON the circuit breaker or replace the fuse. Turn the input
power ON again, and if no output voltage is output, the product
may have failed. Replace the product.
Power
Overload
Boost
protection
Function
operating
Troubleshooting methods
Overload protection
operating (when output
is short-circuited)
・・・・・・
Indicator: Flashing
Signal output: Repeated
conducting/non-conducting
・・・・・・
MOS FET relay
Min. ON time: 5 ms