2.6 MOUNTING THE BOILER

Due care should be taken when lifting the
boilers, with respect to their weights, see
Table 2 on Page 6. Also refer to Section 1.4
Safe Handling.
1. Lift the boiler onto the wall mounting plate as
shown. Note: It is not necessary to hold the
boiler at an angle to engage the wall mounting
plate.
2. Using the remaining coach screws, secure
the bottom of the boiler to the wall through the
attached brackets.
IMPORTANT NOTE It is essential that these bolts
be fitted prior to making up the flow and return
connections to the boiler to prevent the boiler
becoming detached .

2.7 VENTILATION

If installing in a room or internal space then no purpose provided ventilation is required. When installing in a compartment,
the table below details the ventilation requirements in line with BS5440.
Keston ventilation requirements when installed in a compartment up to 70kW (BS5440)
Model
Min Free Area (cm
Keston Heat 45/55 (multiple boiler applications)
Detail reference should be made to BS. 6644 for inputs
between 70kW and 1.8MW (net). In IE refer to the current
edition of I.S.820. The following notes are for general
guidance only:
Installation & Servicing
SECTION 2 - INSTALLATION
To a room or internal space
45 & 45P
2
)
432
55 & 55P
45 & 45P
527
216
If ventilation is to be provided by means of permanent
high and low vents communicating direct with outside air,
then reference can be made to the sizes below. For other
ventilation options refer to BS. 6644. In IE refer to the
current edition of I.S.820.
To outside Air
55 & 55P
263
17