DFC-OEM-DBI
Input: 120-277 V~ 50/60 Hz 1 A
Lutron Digital Link Interface
Output: 18 V- 60 mA
Supplies power to the following devices:
DFCSJ-OEM-OCC
DFCSJ-OEM-RF
when used in conjunction with Lutron EcoSystem LED drivers.
Important Notes:
• For installation by the luminaire manufacturer.
• Use copper conductors only.
• Check to see that the device type and rating is suitable for the application.
• DO NOT install if product has any visible damage.
• If moisture or condensation is evident, allow the product to dry completely
before installation.
• Operate between 32 °F to 140 °F (0 °C to 60 °C), ambient.
• 0% to 90% humidity, non-condensing.
• For indoor use only.
Vive Integral Fixture Control
Fixture Control
30 ft (9 m)
Maximum
Pico Remote
Control
NOTE: Wireless sensors and controls must be located within 60 ft
(18 m) line of sight, or 30 ft (9 m) through walls of each other.
Limited Warranty:
http://www.lutron.com/TechnicalDocumentLibrary/3601321.pdf
FCC / IC Information
This device complies with part 15 of the FCC Rules and Industry Canada license-
exempt RSS standard(s). Operation is subject to the following two conditions:
(1) This device may not cause interference, and (2) this device must accept any
interference, including interference that may cause undesired operation. Modifications
not expressly approved by Lutron Electronics Co., Inc. could void the user's authority
to operate this equipment.
NOTE: This equipment has been tested and found to comply with the limits for
a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a residential
installation. This equipment generates, uses and can radiate radio frequency energy
and, if not installed and used in accordance with the instructions, may cause
harmful interference to radio communications. However, there is no guarantee that
interference will not occur in a particular installation. If this equipment does cause
harmful interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
• Re-orient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the
receiver is connected.
For more information, see
http://www.lutron.com/TechnicalDocumentLibrary/3691039.pdf
Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA
Required Components
For each fixture, you will need:
One Digital Link Interface
At least one EcoSystem driver
+
(DFC-OEM-DBI)
Start Here
Install the Digital Link Interface
1
WARNING! Shock Hazard. May result in serious injury or death.
Turn off power at circuit breaker before installing the unit.
Intended to be installed within the interior of a luminaire (not for external/remote mounting).
A Mount the Digital Link Interface to the interior of the fixture surface using two screws.
B Connect to line and sensor/driver as shown in diagram below.
Fixture Control Digital Link Interface
Neutral
Line
EcoSystem Driver (up to 4)
Pico Remote Control
Radio Powr Savr
(up to 10)
occupancy sensor
(up to 10)
Lutron, Pico, Vice, and EcoSystem are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries. Radio Powr Savr is a trademark of Lutron Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts.
©2014 – 2018 Lutron Electronics Co., Inc.
Customer Assistance | 1.800.523.9466 USA, Canada, and the Caribbean | +1.610.282.3800 Others | www.lutron.com
One Vive Integral Fixture Control
+
Vive Integral Fixture Control with Sensor
(DFCSJ-OEM-OCC)
EcoSystem
Dashed line = Fixture
polarity-free
digital link
S+ (Blue)
S- (Blue)
E1 (Violet)
E2 (Violet)
EcoSystem
polarity-free
digital link
Vive Integral Fixture Control
Link
Test
Radio Powr Savr
Vive Wireless Hub
daylight sensor
(1 maximum)
(1 maximum)
PIR lens
LED/Daylight sensor lens
Button
OR
Vive Integral Fixture Control (RF only)
(DFCSJ-OEM-RF)
Note: Daylighting functionality is not available
in the DFCSJ-OEM-RF

Dimensions

Measurements shown as: inches (mm)
Dia. 0.21 (5.3)
4.60
(116.9)
5.06
(128.5)
Notes:
For more information on Lutron wireless fixture controls, see P/N 3691039 on www.lutron.com
For DFCSJ-OEM-OCC or DFCSJ-OEM-RF installation instructions visit www.lutron.com
LED lens
Button
1.17
(29.7)
0.81
(20.5)

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DFC-OEM-DBI and is the answer not in the manual?

Questions and answers

Summary of Contents for Lutron Electronics DFC-OEM-DBI

  • Page 1 • Re-orient or relocate the receiving antenna. Link Test • Increase the separation between the equipment and receiver. • Connect the equipment into an outlet on a circuit different from that to which the Notes: receiver is connected. Pico Remote Control Radio Powr Savr Radio Powr Savr Vive Wireless Hub For more information on Lutron wireless fixture controls, see P/N 3691039 on www.lutron.com (up to 10) occupancy sensor daylight sensor (1 maximum) For more information, see (up to 10) (1 maximum) For DFCSJ-OEM-OCC or DFCSJ-OEM-RF installation instructions visit www.lutron.com http://www.lutron.com/TechnicalDocumentLibrary/3691039.pdf Lutron, Pico, Vice, and EcoSystem are trademarks of Lutron Electronics Co., Inc., registered in the U.S. and other countries. Radio Powr Savr is a trademark of Lutron Electronics Co., Inc. NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts. Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 USA ©2014 – 2018 Lutron Electronics Co., Inc.
  • Page 2 Link Test Remarques : • Réorientez ou repositionnez l’antenne réceptrice. • Augmentez la séparation entre l’équipement et le récepteur. Pour plus d’informations sur les commandes de luminaire sans fil de Lutron, voir n de • Connectez l’équipement à une prise électrique se trouvant sur un circuit différent de pièce 3691039 sur www.lutron.com Télécommande Pico Détecteur d’occupation Détecteur de lumière du Hub sans fil Vive celui où le récepteur est connecté. (jusqu’à 10) Radio Powr Savr jour Radio Powr Savr (1 maximum) Pour les instructions d’installation de DFCSJ-OEM-OCC ou DFCSJ-OEM-RF, consultez Pour plus de renseignements, consultez (jusqu’à 10) (1 maximum) www.lutron.com http://www.lutron.com/TechnicalDocumentLibrary/3691039.pdf Lutron, Pico, Vive et EcoSystem sont des marques commerciales de Lutron Electronics Co., Inc., enregistrées aux États-Unis et dans d’autres pays. Radio Powr Savr est une marque déposée de Lutron Electronics Co., Inc. NEC est une marque déposée de la National Fire Protection Association, Quincy, Massachusetts. Lutron Electronics Co., Inc. 7200 Suter Road, Coopersburg, PA 18036-1299, États-Unis ©2014 – 2018 Lutron Electronics Co., Inc.
  • Page 3 Link Test • Reorientar o reubicar la antena receptora. • Aumentar la separación entre el equipo y el receptor. Notas: • Conectar el equipo a un tomacorriente que corresponda a un circuito diferente de Para obtener más información sobre los controles de dispositivos inalámbricos de Lutron, aquel al cual está conectado el receptor. Control remoto Pico Sensor de ocupación Sensor de luz diurna Hub Vive inalámbrico consulte la N/P 3691039 en www.lutron.com (hasta 10) Radio Powr Savr Radio Powr Savr (1 máximo) Para obtener información adicional, consulte (hasta 10) (1 máximo) Para obtener las instrucciones de instalación de la DFCSJ-OEM-OCC o la DFCSJ-OEM-RF http://www.lutron.com/TechnicalDocumentLibrary/3691039.pdf visite www.lutron.com Lutron, Pico, Vive y EcoSystem son marcas comerciales de Lutron Electronics Co., Inc. registradas en E.U.A. y otros países. Radio Powr Savr es una marca de comercial de Lutron Electronics Co., Inc. NEC es una marca comercial registrada de la National Fire Protection Association, Quincy, Massachusetts. Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299, E.U.A. ©2014 – 2018 Lutron Electronics Co., Inc.
  • Page 4 Link Test Notas: • Reorientar ou reposicionar a antena de recepção; Para obter mais informações sobre os controles de luminária sem fio da Lutron, • Aumentar a distância entre o equipamento e o receptor; consulte a P/N 3691039, no site www.lutron.com • Conectar o equipamento em uma tomada com circuito diferente do receptor. Controle sem fio Pico Sensor de ocupação Sensor de luz natural Hub sem fio Vive (até 10) Radio Powr Savr Radio Powr Savr (no máx. 1) Para ver instruções de instalação dos controles DFCSJ-OEM-OCC ou DFCSJ-OEM-RF, Para obter mais informações, consulte o documento (até 10) (no máx. 1) visite o site www.lutron.com http://www.lutron.com/TechnicalDocumentLibrary/3691039.pdf Lutron, Pico, Vive e EcoSystem são marcas comerciais da Lutron Electronics Co., Inc., registrada nos EUA e em outros países. Radio Powr Savr é uma marca comercial da Lutron Electronics Co., Inc. NEC é uma marca comercial registrada da National Fire Protection Association, de Quincy, Massachusetts, EUA. Lutron Electronics Co., Inc. 7200 Suter Road Coopersburg, PA 18036-1299 EUA ©2014 – 2018 Lutron Electronics Co., Inc.