Pepperl+Fuchs HD2 Series Manual page 13

Compact fieldbus power hub, generic interface
Table of Contents

Advertisement

Compact Fieldbus Power Hub,Generic Interface
Specification
Vibration resistance
Pollution Degree
Corrosion resistance
Mechanical specifications
Connection type
Degree of protection
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC
Standard conformity
Electromagnetic compatibility
Degree of protection
Fieldbus standard
Shock resistance
Vibration resistance
Motherboard Types MBHC-FB-8R*
Supply
Connection
Rated voltage
Rated current
Power loss
Indicators/operating means
Fault signal
Isolated Power Supply Module Type HCD2-FBPS-1.500
Supply
Rated voltage
Power loss
Fieldbus interface
Rated voltage
Rated current
Short-circuit current
Indicators/operating means
LED ERR
LED PWR
Data for application in connection with Ex-areas
Outputs
Voltage
Isolated Power Supply Module Type HCD2-FBPS-1.23.500
Supply
Rated voltage
Power loss
1 g , 10 ... 150 Hz
max. 2, according to IEC 60664
acc. to ISA-S71.04-1985, severity level G3
pluggable , screw terminal or spring terminal
IP20
EN 61326-1:2013
NE 21:2011
IEC 60529
IEC 61158-2
EN 60068-2-27
EN 60068-2-6
redundant
19.2 ... 35 V SELV/PELV
16 A
typ. 0.4 W per segment
VFC alarm 1 A, 50 V DC, normally closed
19.2 ... 35 V DC
typ. 1.6 W
28 ... 30 V
500 ... 10 mA
550 mA
red flashing: short-circuit or undervoltage at output
green if U
> 28 V
out
30 V
19.2 ... 35 V DC
typ. 1.6 W
13