Wall and Ceiling Troughs
Thermo King recommends enclosed wall or ceiling troughs be used for SPECTRUM multi-temperature applications.
Troughs not only protect refrigeration tubes and electrical harnesses from damage, but also help prevent air leakage
between compartments.
The following installation standards are recommended:
•
Only one trough (Wall or Ceiling) is required.
•
Refrigeration tubes should be routed neatly in the trough.
•
Refrigeration tubes should be secured by clamps every 600 mm (24.00 in.) inside the trough.
•
Electrical harness should be secured by clamps or tie bands every 600 mm (24.00 in.) inside the trough.
•
Insulate all hot gas and suction refrigeration tubes inside the trough.
•
Trough covers are recommended to protect refrigeration tubes and electrical harnesses from damage.
203 mm
(8.00 in.)
1.
Suction Tube
2.
Hot Gas Tube
TK 56701-1-IM-EN
Figure 33. Refrigerant Tubing and Electrical Wiring Details Shown
1
1
2
3
4
36 mm
(1.40 in.)
E E v v a a p p o o r r a a t t o o r r I I n n s s t t a a l l l l a a t t i i o o n n S S t t a a n n d d a a r r d d s s
4
3
RCS1140-3
3.
Liquid Tube
4.
Electrical Harnesses