Programmable Controller (40Vm900003) - Carrier 40VMM Series Installation And Maintenance Instructions Manual

Medium static duct indoor unit for variable refrigerant flow (vrf) systems
Hide thumbs Also See for 40VMM Series:
Table of Contents

Advertisement

Click TEMP. UP or TEMP. DOWN to change 00 to the
desired address as shown in Fig. 37. Press OK to confirm and
exit the setting interface.
MODE
TEMP. UP
ROOM TEMP.
FAN
TEMP. DOWN
Fig. 37 — Non-Programmable Controller
(40VM900002) Setting IDU Address

Programmable Controller (40VM900003)

When setting an address, connect only one wired controller to
an indoor unit.
1. Press FAN and BACK simultaneously for 5 seconds to
access parameter settings as shown in Fig. 38.
MODE
FAN
TEMP. DOWN
Fig. 38 — Programmable Controller
(40VM900003)
ON/OFF
TIMER
SWING
OK
TEMP. UP
ON/OFF
MENU
OK
BACK
IDU Addressing Menu
2. Press TEMP. UP or TEMP. DOWN to move the cursor
and choose IDU ADDRESSING. Press MENU/OK to
access this setting.
3. Press TEMP. UP or TEMP. DOWN to choose the
address you want to set (see Fig. 39). Press MENU/OK
to send this address to the IDU.
MODE
FAN
Fig. 39 — Programmable Controller
(40VM900003)
4. Press BACK twice or wait 30 seconds to automatically
exit the parameter settings menu.
22
TEMP. UP
ON/OFF
MENU
OK
TEMP. DOWN
BACK
Setting IDU Address