Appendix A - Dip Switch Settings - Carrier 40VMM Series Installation And Maintenance Instructions Manual

Medium static duct indoor unit for variable refrigerant flow (vrf) systems
Hide thumbs Also See for 40VMM Series:
Table of Contents

Advertisement

There are 2 DIP switches on the main board. Figures A and
B show the settings for each parameter controlled by a switch.
Switches are shown in the default settings.
v
ON
OFF
1 2 3 4
a40-1923
POSITION 1 — START-UP
OFF
— Auto Addressing Mode (Default)
ON
— Factory Test Mode
ON
OFF
1 2 3 4
a40-1923
POSITION 2 — MODE
OFF
— Normal Mode (default)
ON
— Factory Self-Checking Mode
ON
OFF
POSITION 3 — NOT USED
ON
OFF
1 2 3 4
a40-1923
POSITION 4 — INDOOR UNIT IDENTIFICATION
OFF
— Standard Indoor Unit (Default)
ON
— Mode Priority Indoor Unit (HP only)
(IDU address must be 63)
Fig. A — SW1 Settings
© Carrier Corporation 2018
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 18-40VMM001-02
APPENDIX A — DIP SWITCH SETTINGS
Printed in U.S.A.
Form 40VMM-2SI
ON
OFF
1 2
a40-1925
POSITION 1, 2 — NOT USED
Fig. B — SW8 Settings
Terminal J1 is located on the main control board. When J1
jumper is not in place, Auto Restart function is enabled. When
J1 jumper is in place, Auto Restart function is disabled. The
default setting for J1 is without the jumper in place.
Pg 25
1-18
Replaces: 40VMM-1SI