Replacement Parts - Carrier 40VMM Series Installation And Maintenance Instructions Manual

Medium static duct indoor unit for variable refrigerant flow (vrf) systems
Hide thumbs Also See for 40VMM Series:
Table of Contents

Advertisement

ERROR
DESCRIPTION
DD
Heating / Cooling Mode Conflict
Communication Error Between
E1
Indoor & Outdoor Unit
E2, E4,
Check Temperature Sensor
E5
E6
DC Fan Motor
E7
EEPROM Error (Data Storage)
Communication Error Between
E9
Indoor Unit and Controller
EB
EEV Error
ED
Outdoor Unit Error
EE
Condensate Error
No Address When Power ON for first
FE
time
UU
MDC Auto System-Check Mode
LEGEND
EEV
— Electronic Expansion Valve
Electronically Erasable Programmable Read-only
EEPROM —
Memory
MDC
— Multiport Distribution Controller
PC
— Process Controller
Table 6 — Troubleshooting
POSSIBLE CAUSES
System is in cooling or fan only mode and
heating signal is received from a unit on the
system.
System is in heating mode and cooling
signal is received from a unit in the system.
Signal wires are short-circuited or
disconnected.
Signal wire close to electromagnetic
source.
PC board fault.
Loose connection at port on PC board.
Sensor is short-circuited.
PC board fault.
Operating beyond limits.
DC motor fault.
PC board fault.
Chip or PC board fault.
Signal wires are short-circuited or
disconnected.
Signal wires close to electromagnetic
source.
PC board fault.
EEV wires are short-circuited or
disconnected.
EEV stop.
PC board fault.
Outdoor unit fault.
Loose connection or disconnected.
Water level float is stuck.
Trap slope is too steep.
Drain pipe is too long.
Drain pump faulty.
Indoor unit without address.
MDC fault
Replacement Parts —
and unit serial number when ordering replacement parts or
contacting the factory about the unit. This information can be
found on the serial plate attached to the unit. See Fig. 41.
24
POSSIBLE SOLUTIONS
All units should be in cooling mode for system to
stay in cooling mode.
All units should be in heating mode.
Check or reconnect signal wire.
Distance signal wires from electromagnetic
source.
Replace PC board.
Tighten the connection at port on PC board.
Using multi-meter, measure resistance of the
sensor. If the resistance is £ 100 ohms, change
the sensor.
Replace PC board.
Check and correct external static pressure on the
unit.
Replace DC motor.
Replace PC board.
Replace PC board.
Check or reconnect signal wires.
Distance signal wires from electromagnetic
source.
Replace PC board.
Replace EEV wires.
Replace EEV.
Replace PC board.
Refer to outdoor unit troubleshooting guide.
Tighten the connection or reconnect at port on
PC board.
Inspect the slope.
Adjust the trap slope.
Adjust the length of drain pipe.
Replace the drain pump.
Run automatic addressing option at the outdoor
unit.
Use remote wireless or wired controller to
readdress indoor unit.
Refer to MDC troubleshooting guide.
Quote the unit model number
CONFORMS TO UL STD 1995
CERTIFIED TO CSA STD.
C22. 2 No. 236
ELECTRIC CHARACTERISTICS ARE
ONLY FOR INDOOR UNIT.
MEDIUM STATIC DUCT UNIT
40VMM007A--3
MODEL
POWER SUPPLY
208/230V-1Ph-60Hz
MINIMUM CIRCUIT AMPACITY
1.25 A
MAX FUSE OR HACR BREAKER
15 A
FLA
1 A
FAN MOTOR
OUTPUT
100W (1/6HP)
REFRIGERANT
R410A
HIGH
580 PSIG
DESIGN
PRESSURE
LOW
320 PSIG
SERIAL NO.
1716V00001
Carrier Corporation
Fig. 41 — Unit Serial Plate (Example)