Carrier 40VMM Series Installation And Maintenance Instructions Manual page 9

Medium static duct indoor unit for variable refrigerant flow (vrf) systems
Hide thumbs Also See for 40VMM Series:
Table of Contents

Advertisement

Fan Characteristics Curve
0.68
0.64
0.60
0.56
0.52
0.48
0.44
0.40
0.36
0.32
0.28
0.24
0.20
0.16
0.12
0.08
0.04
0.00
600
800
Air Flow (CFM)
RANGE OF AVAILABLE AIRFLOW RATE IN
FAN
ESP
Max Point
SPEED
Max
SP
CFM
(in.)
0.10
H
1265
0.02
0.20
H
1265
0.12
0.30
H
1265
0.24
0.40
H
1265
0.33
0.50
H
1265
0.44
0.60
H
1265
0.52
LEGEND
ESP
— External Static Pressure
SP
— Static Pressure
Fig. 10 — Size 030 Fan Curves
1070
1,000
1,200
H-SPEED
Mid Point
Min Point
Mid
SP
Min
SP
CFM
(in.)
CFM
(in.)
1070
0.10
935
0.16
1070
0.19
935
0.24
1070
0.30
935
0.34
1070
0.38
935
0.42
1070
0.49
935
0.53
1070
0.59
935
0.64
Fan Characteristics Curve
0.64
0.60
0.56
0.52
0.48
0.44
0.40
0.36
0.32
0.28
0.24
0.20
0.16
0.12
0.08
0.04
0.00
650
850
Air Flow (CFM)
RANGE OF AVAILABLE AIRFLOW RATE IN
FAN
ESP
Max Point
SPEED
Max
CFM
0.10
H
1366
0.20
H
1380
0.30
H
1380
0.40
H
1380
0.50
H
1380
0.60
H
1380
LEGEND
ESP
— External Static Pressure
SP
— Static Pressure
Fig. 11 — Size 036 Fan Curves
9
1200
1,050
1,250
1,450
H-SPEED
Mid Point
Min Point
SP
Mid
SP
Min
(in.)
CFM
(in.)
CFM
0.00
1200
0.09
1020
0.11
1200
0.21
1020
0.21
1200
0.28
1020
0.34
1200
0.40
1020
0.44
1200
0.48
1020
0.50
1200
0.56
1020
SP
(in.)
0.16
0.26
0.34
0.46
0.55
0.62

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

40vmm007a series40vmm048a series

Table of Contents