3-3 Test Input Function

It is the function to check normal operation by turning ON / OFF control outputs 1 / 2 (OSSD 1 / 2)
of the controller without generating a liquid leak condition at the sensor.
When the test input terminal between T1 and T2 is open, valid operation can be selected, and
when it is shorted, invalid operation (normal operation) can be selected.
Use a conductor (contact, copper wire, etc.) for short-circuit. A semiconductor (transistor) etc.
may not ensure normal operation.
<Time chart for manual reset selection>
Open
Reset input
Short-
circuit
Test input
Control output 1 / 2
(OSSD 1 / 2)
<Time chart for auto reset selection>
Test input
Control output 1 / 2
(OSSD 1 / 2)
© Panasonic Industriar Devices SUNX Co., Ltd. 2016
30ms or more
ON
OFF
50ms or less
ON
OFF
ON
OFF
50ms or less
30ms or more
140ms or less
ON
OFF
Do not use the test input function for the purpose of stopping the machine in
which this device is mounted. Otherwise, death or injury may occur.
140ms or less
Functions
23