TECHNICAL DATA SPECIFICATIONS
Fuel
F3 Firing rate - Effective Output
F5 Firing rate - Effective Output
Voltage (single phase)
F3 Absorbed electrical power
F5 Absorbed electrical power
Motor (rated)
Capacitor
Pump pressure
Primary control
Ignition transformer

BURNER DIMENSIONS

Model
A
Inches
8 15/32
F3
mm
215
Inches
9 11/64
10 11/16
F5
mm
233
E1: 10-inch long (254mm) tubes are also available.

BURNER COMPONENTS IDENTIFICATION

1
2
3
4
20101936

BURNER COMPONENTS

1 Lockout indicator lamp and reset
button
2 Primary control
3 Primary control sub-base
4 Pump pressure regulator
5 Motor
6 Air adjustment and shutter
7 Electronic air shutter assembly
8 Combustion head
No heavier than # 2 fuel oil
0.50 to 0.95 US GPH - 70,000 to 133,000 BTU/h
0.75 to 1.65 US GPH - 105,000 to 231,000 BTU/h
120V 60Hz (+ 10% - 15%)
155 Watts
175 Watts
3250 rpm Run Current 2.2 AMP
12.5 Microfarads
130 to 200 psig
RIELLO 530 SE/C
8kV 16mA
B
C
D
9 59/64
6 15/32
3 1/2
252
164
89
7 3/32
3 1/2
272
180
89
7
6
5
9 Semi flange 2 pieces
10 Mounting flange with gasket
11 Supply fuel line port
12 Pump valve (coil)
13 Vacuum gauge port
14 Pressure gauge and bleeder port
15 Return fuel line port
16 Turbolator adjustment screw
17 Air tube cover
E
F
6
8 29/32
152
226
6
9 13/32
152
239
9
8
10
11
15
2
E
E1
17
16
12
13
14
5 1 / 2 " - 140 mm
7 1 / 2 " - 190 mm
8 15 / 32 " - 215 mm
B
F
D7352
D7351
2903223