Amulet Installation Instructions - Riello F3 Installation, Use And Maintenance Instructions

Single stage operation oil burners
Hide thumbs Also See for F3:
Table of Contents

Advertisement

Available languages

Available languages

AMULET INSTALLATION INSTRUCTIONS

(Required on some models)
The amulets provided have been selected by Riello to protect the
combustion tube from hot exhaust gases and flame. This protec-
tion may be needed in applications where the combustion tube
opening in the combustion chamber refractory is larger than the
tube outside diameter.
The amulet has been sized to fit Riello Model 40 sizes F3 and F5
plus the Riello Model R35.
When installing this amulet, handle it carefully.
Do not exert undue pressure when pushing the amulet over the
combustion tube.
Excessive force can result in a broken amulet!
If the amulet will not fit easily onto the tube, remove a small amount of the inner diameter with a sharp knife to provide
the necessary clearance.
The diagram below shows the proper position of the amulet after installation.
LOW PRESSURE
AIR TUBE
Increase in pressure
down air tube due
to increase in
combustion chamber
pressure
2903223
NO AMULET
FLUE GASES
Tapered combustion
chamber causes increase
in pressure inside
HEAT
HIGH PRESSURE
HEAT
Increase in pressure down
air tube due to increase
in combustion chamber
pressure
Amulet shown in the
flush mounted position
Head receeded
1/4 inch max.
LOW PRESSURE
AIR TUBE
Amulet helps prevent
not gases from
travelling down
air tube
S7941
5
D7285
AMULET
FLUE GASES
Tapered combustion
chamber causes increase
in pressure inside
HEAT
HIGH PRESSURE
HEAT
Increase in pressure down
air tube due to increase
in combustion chamber
pressure
GB