To control wall-mounted Combi heaters and heaters
and steamers as separate units (Harvia SS20) in the
sauna by means of the control unit a temperature
sensor, connected to the unit, must be mounted
on the sauna wall above the heater in line with
the midpoint of the heater's breadth and 100 mm
below the ceiling.
The humidity sensor must be mounted on the
sauna wall as far away as possible from the heater
and 500–700 mm below the ceiling.
When the C105S control unit is being used to
control a Combi heater standing on the floor or
1
BLUE/BLAU
2
WHITE/WEIß
3
RED/ROT
4
YELLOW/GELB
BLUE/BLAU
5
WHITE/WEIß
6
RED/ROT
7
GREEN/GRÜN
8
GRAY/GRAU
9
YELLOW/GELB
10
6 x 0,25 mm²
2. HUMIDITY SENSOR
FEUCHTESENSOR
PERMITTED AREA
ERLAUBTE FLÄCHE
2. HUMIDITY SENSOR
FEUCHTESENSOR
Figure 7A.
The location of the C105S control unit temperature and humidity sensor boxes when used with wall-
mounted heaters.
Abbildung 7A.
Ort für das Temperaturfühler- sowie Feuchtesensorgehäuse des Steuergerätes C105S bei
wandmodellen der Saunaöfen.
4 x 0,25 mm²
C105S
1. TEMPERATURE SENSOR
TEMPERATUR FÜHLER
3.3. Montage der Fühlergehäuse
Zur Steuerung sowohl des Saunaofens als auch des
separaten Verdampfers der Wandmodelle der Com-
bi-Saunaöfen (Harvia SS20) mit dem Steuer gerät
C105S muss der an das Steuergerät anzuschließen-
de Temperaturfühler oberhalb des Saunaofens an der
Saunawand auf der Mittellinie der Saunaofenbreite
100 mm unterhalb der Decke installiert werden.
Der Feuchtesensor muss an der Saunawand mög-
lichst weit entfernt vom Saunaofen 500–700 mm
unterhalb der Decke installiert werden.
Zur Steuerung eines Standmodells des Combi
Saunaofens oder eines separaten Verdampfers und
min. 150
1. TEMPERATURE SENSOR
TEMPERATURFÜHLER