Echelon Network Termination - Emerson E2 Einstein Manual

Controller wiring practices
Hide thumbs Also See for E2 Einstein:
Table of Contents

Advertisement

6.2.1. Echelon Network Termina-
tion
Echelon networks require the devices on each
end of the daisy chain to be terminated with a 105-
ohm resistor across the signal-carrying leads. Most
CPC-manufactured Echelon devices have on-board
termination jumpers that, when set to the "termi-
nated" position, provide the required termination
resistance (refer to the device's own installation doc-
umentation). If the device does not have termination
jumpers, CPC offers an Echelon termination block
(P/N 535-2715) that may be wired in series right
before the end device (see Figure 6-7) or at the end
of an Echelon network run (necessary for TD3 instal-
lations) (Figure 6-8). The termination block provides
the necessary 105-ohm resistance for network termi-
nation.
Figure 6-7 - Echelon Termination Block (P/N 535-2715)
Figure 6-8 - Termination Block Usage With TD3s
Echelon Networking
Network Structure, Biasing, and Termination Resistance • 9