Download Print this page
Emerson E2 Enhanced RX Technical Bulletin

Emerson E2 Enhanced RX Technical Bulletin

With rmcc/bec/bcu retrofitting

Advertisement

Quick Links

E2 Enhanced RX and BX Controllers and
RMCC/BEC/BCU Retrofitting
Technical Bulletin
Overview
This technical bulletin describes E2E retrofitting of supermarkets with existing REFLECS controllers.
STEP 1: Preparing for Retrofit
When replacing a REFLECS unit with an E2E, there are several major differences that must be taken into
account.
1. All REFLECS units are powered by 110/220VAC line voltage. E2E controllers are powered by 24VAC
non center-tapped transformers. Refer to the E2E User's Manual (P/N 026-1614 Rev 5 or later) for more
information on powering the E2E controller.
2. REFLECS units use an RS485 (COM B) network to connect to a 485 Alarm Panel. E2E does not support
the 485 Alarm Panel.
3. REFLECS units use an RS232 (COM C) host network to connect all units to a modem for alarm dial-out.
E2Es may use either Echelon or Ethernet for box-to-box communication. The existing host network
wiring may not be used for E2E box-to-box communication - you will either have to rewire using
approved Echelon network wire, or wire CAT 5 cable to an approved network router or switch. Refer
to the E2E User's Guide for more information on box-to-box wiring.
4. COM A and COM D networks (the RS485 I/O networks) use the same wire and polarity for both the
REFLECS and E2E controllers. No rewiring of the I/O network will be necessary; just unplug the COM A
and/or COM D connectors, and plug them into the I/O port(s) on the E2E PIB (see "Transferring the
COM A and COM D Networks" below).
STEP 2: Transferring the COM A and COM D Networks
The COM A and COM D I/O networks on the RMCC/BEC/BCU are where connections to all I/O devices, such
as 16AIs and 8ROs are made. The two networks are interchangeable, each one capable of connecting up to
31 devices.
Document Part # 026-4157 Rev 0 19-FEB-2016
©2016 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use.
Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
Page 1 of 4

Advertisement

loading

Summary of Contents for Emerson E2 Enhanced RX

  • Page 1 31 devices. Document Part # 026-4157 Rev 0 19-FEB-2016 Page 1 of 4 ©2016 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use. Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
  • Page 2 Refer to the E2E User’s Manual (P/N 026-1614 Rev 5 or later) for expanded communication setup information. Document Part # 026-4157 Rev 0 19-FEB-2016 Page 2 of 4 ©2016 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use. Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
  • Page 3 You will need to set two parameters in the C3: Serial tab. Document Part # 026-4157 Rev 0 19-FEB-2016 Page 3 of 4 ©2016 Emerson Climate Technologies Retail Solutions, Inc. This document may be photocopied for personal use. Visit our website at http://www.emersonclimate.com/ for the latest technical documentation and updates.
  • Page 4 The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Emerson Climate Technologies Retail Solutions, Inc. and/or its affiliates (collectively “Emerson”), reserves the right to modify the designs or specifications of such products at any time without notice. Emerson does not assume responsibility for the selection, use or maintenance of any product.

This manual is also suitable for: