Hisense AHM-080FJFAA Operation Installation Maintenance Manual page 16

Multi-split air conditioner, water module
Table of Contents

Advertisement

5.1.3.3 Floor heating
Step 1
Power on, wire remote controller will run at the
default state, and previously running function may
appear on the LCD screen. According to the
actually mounted terminals, refer to "5.1.7 In-situ
Settings" for the settings; press the function key ⑥,
floor heating appears on the LCD screen;
continuously press the function key ⑥, the icon will
change between floor heating
until the floor heating is selected.
Heating
Floor Heating
Temperature Code
Floor Heating
Step 2
If the water outlet set temperature is increased,
press " " of the temperature setting key ③; if it
is reduced, press " " . For heating, the highest
water outlet set temperature is 55°C, and the
lowest set temperature is 20°C.
● In the in-situ settings of the wire controller, it
may also set the automatic regulation mode of
water outlet temperature. After setting, the water
outlet temperature can be automatically
regulated according to change in outdoor
environmental temperature (OTC), see detals in
"5.1.7 In-situ Settings". The settings include
automatic regulation function active/inactive
("b9"), beginning and ending time each day
("C1" "C2"), lowest and highest environmental
temperatures ("C3", "C4") and the set water
temperatures corresponding to the highest and
lowest environmental temperatures ("C5", "C6").
● OTC (outlet temperature control) function.
Under this function, system water outlet
temperature will be automatically controlled
between Lo_Ta and Hi_Ta according to change
in the environmental temperature. See the
details about temperature control below.
and water tank
10
Two
Set Water Outlet Temperature
Lo_Two
Hi_Two
Lo_Ta
Hi_Ta
Lo_Two: Low Environmental Temperature
Set Value (C5)
Hi_Two: High Environmental Temperature
Set Value (C6)
Lo_Ta: Low Environmental Temperature (C3)
Hi_Ta: High Environmental Temperature (C4)
Two: Set Water Outlet Temperature
Ta: Outdoor Environmental Temperature
● When the machine is at the automatic water
outlet temperature control state, the set water
outlet temperature is automatically calculated
by the wire controller. User may adjust ±8°C
based on the calculation result, but if the
adjusting range exceeds the upper and lower
limits of temperature settings, the upper and
lower limits should prevail.
Set Temperature
Outdoor Environmental Temperature
● When OTC starts, the automatic run icon will
display to indicate the OTC function. After the
timing ends, automatic run icon will disappear.
Appear During
Automatic Run
Step 3
Press the
key
ON/OFF
the machine begins running.
Ta Environmental Temperature
A
B
⑧, the LED lamp on, and