Type CPV...−GE−ASI−4E3A−Z M8
AS−Interface bus connection
voltage range
(protected against incorrect polarity)
residual ripple
max. current consumption at −5 °C
all inputs in 0−status
all inputs in 1−status, no current
consumption by sensors
all inputs in 1−status, max. current
consumption by sensors
Load voltage connection
rated value
(protected against incorrect polarity)
residual ripple
Current consumption for 3 valves
(at 24 V)
when switching on
after current drop (stationary)
Valves (see Pneumatics manual)
Digital inputs
design
logic level
reference potential
response delay
1)
e.g. switches
Festo CPV..−GE−ASI−4E3A−... 0404NH English
DC 26.5 ... 31.6 V
CPV10−... CPV14−...
7mA
35mA
1)
137mA
DC 21.6 ... 26.4 V
4 Vss
CPV10−... CPV14−...
108 mA
42 mA
Watchdog function active
after approx. 40 ... 100 ms
(see 3.5)
4 inputs based on IEC
1131−2 type 2
DC 24 V, PNP, Status dis
play (LED)
ON: +11 ... +30 V
OFF: −30 ... +5 V
0V
typ. 3 ms (at 24V)
20 mVss
7mA
35mA
137mA
176 mA
72 mA
25