3.4 Connecting sensors (PNP inputs)
For connecting sensors use cable type KM8−M8−GSGD−...
and plugs with union nut, M8x1 thread.
Fasten the plugs with the aid of the union nut in order to
prevent unintentional loosening, e.g. due to shock. Seal
the unused sensor connections with the protective caps
supplied. Only in this way can you comply with protection
class IP65.
Please note
The inputs have been based on the IEC1131−2 type
02.
The inputs are protected against short circuits. If a
short circuit occurs, the slave will be switched off.
The AS−Interface master regards this slave as mis
sing. When the short circuit has been eliminated, the
slave responds immediately as being operative.
1
Pin assignment:
1: 24 V
3: 0 V
4: Input Ix+3
20
Festo CPV..−GE−ASI−4E3A−... 0404NH English