Component Identification; Led Function - M-system R6-NE1 Instruction Manual

Ethernet interface module
Table of Contents

Advertisement

COMPONENT IDENTIFICATION

SIDE VIEW
■ SIDE DIP SW
(*) Factory setting
• Data Allocation Mode: SW1, SW2
DATA ALLOCATION MODE
1
2 (*)
• LED Function: SW3

LED FUNCTION

RUN:
Green ON in normal communications
(*)
ERR:
Green ON/blinks in an abnormality
RUN:
Red ON when receiving
ERR:
Red ON when transmitting
Note: Be sure to set unused SW4 through 8 to OFF.
PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R6CON for detailed operation.
■ INTERFACE MODULE SETTING
PARAMETER
Communication Failure Detection Time
IP address
Port 1
Port 2
Port 3
Port 4
TCP connection close time 1
TCP connection close time 2
TCP connection close time 3
TCP connection close time 4
Card map
1 2 3 4 5 6 7 8
SW1
SW2
= ON, Blank = OFF
SW3
= ON, Blank = OFF
AVAILABLE RANGE
0.2 – 3200.0 (sec.)
255.255.255.255
0 – 32767
0 – 32767
0 – 32767
0 – 32767
1.0 – 3200.0 (sec.)
1.0 – 3200.0 (sec.)
1.0 – 3200.0 (sec.)
1.0 – 3200.0 (sec.)
00000000 to FFFFFFFF
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
FRONT VIEW
RUN Indicator LED
ERR Indicator LED
Configuration Jack
RJ-45 Connector
■ ETHERNET INDICATORS
ID
COLOR
FUNCTION
LINK
Red
ON at LINK
DPLX
Red
ON with full-duplex communication
LINK10
Red
ON with 10 Mbps connection
LINK100
Red
ON with 100 Mbps connection
COL
Red
Blinking when collision occurs
DEFAULT SETTING
3.0 (sec.)
192.168.0.1
502
502
502
502
180.0 (sec.)
180.0 (sec.)
180.0 (sec.)
180.0 (sec.)
FFFFFFFF
R6-NE1
Not used
Not used
Ethernet LED
LINK
DPLX (Duplex)
COLL (Collision)
LINK10 (10Mbps)
LINK100
(100Mbps)
EM-7787 Rev.7 P. 3 / 9