M-system R7G4HH-A-YVF4 Instruction Manual

Hi-speed link system i/o module (high-speed dc voltage output, 4 points, isolated, screw terminal block)

Advertisement

Quick Links

INSTRUCTION MANUAL
HI-SPEED LINK SYSTEM I/O MODULE
(high-speed DC voltage output, 4 points, isolated, screw terminal block)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
High-speed DC voltage output module ..............................(1)
DIN rail mounter slider ......................................................(2)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MODEL
POINTS OF CAUTION
■ CONFORMITY WITH EU DIRECTIVES
• Use dual-shield cables (Shinko Seisen Industry Model
ZHY262 PBA) for the network. If it is not sufficient, use
a ferrite core (Kitagawa Industries Model GRFC-13) for
the network cable.
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V DC ±10%, approx. 70mA
■ GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply and output signal for safety.
• Before you remove the terminal block or mount it, make
sure to turn off the power supply and output signal for
safety.
• DO NOT set the switches on the module while the power
is supplied. The switches are used only for maintenance
without the power.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
• Be sure to close the terminal cover for safety.
■ AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
R7G4HH-A-YVF4
EM-7777-F Rev.2 P. 1 / 9

Advertisement

Table of Contents
loading

Summary of Contents for M-system R7G4HH-A-YVF4

  • Page 1 (high-speed DC voltage output, 4 points, isolated, screw terminal block) BEFORE USE ..POINTS OF CAUTION Thank you for choosing M-System. Before use, please check ■ CONFORMITY WITH EU DIRECTIVES contents of the package you received as outlined below. • Use dual-shield cables (Shinko Seisen Industry Model If you have any problems or questions with the product, ZHY262 PBA) for the network.
  • Page 2: Component Identification

    Turns on when output value is not greater than -15% or not lower than 115%. Station Address Setting (LSD) Station Address Setting (MSD) EM-7777-F Rev.2 P. 2 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 3 VH2 Wide span volt. 2 Narrow span volt. 2 No connection COM3 Common 3 VH3 Wide span volt. 3 Narrow span volt. 3 No connection EM-7777-F Rev.2 P. 3 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 4 ■ NETWORK Recommended cable connector: TM21P–88LP (Hirose Electric) (not included in the package) • Communication connector pin assignment Blank: 3, 4 – 5, 6 pair wiring   (M-System HLS related device standard pin assignment) Full-duplex communication Half-duplex communication 12345678 12345678 1.
  • Page 5: Mounting Instructions

    1) Insert the longer DIN rail mounter slider until it clicks twice, as shown below. 2) Mount the unit with M4 screws referring the Mounting Requirements. (Torque: 1.4 N·m) EM-7777-F Rev.2 P. 5 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 6: Terminal Connections

    15 16 17 18 DIN rail 4.5 (.18) dia (35mm wide) 4 (.16) deep 4(.16) 4(.16) 7-M3 power supply 18-M3 Output terminal screws terminal screws EM-7777-F Rev.2 P. 6 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 7 Caution: FE terminal is NOT a protective conductor terminal. • 3, 4 – 5, 6 PAIR WIRING • 4, 5 – 3, 6 PAIR WIRING (M-System HLS related device standard pin assignment) (Ethernet cable pin assignment) OUTPUT 0 OUTPUT 0...
  • Page 8: Communication Cable Connections

    The separable terminal of the unit is 2 piece constructions. It is possible to remove the terminal by loosening two screws of terminal alternately. EM-7777-F Rev.2 P. 8 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 9 ADD.n+6 Unused (ADD.n+3) Data is represented in 16-bit binary. Negative value is represented in 2's complements. Assignment for half-duplex communication in parentheses. EM-7777-F Rev.2 P. 9 / 9 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...