11.4
Building Technologies
CPS Fire Safety
Configuring logging function on the fly
Note: The reset of the unit results in restoring the original logging configuration
saved in Composer.

The NK823x Web Server

The NK823x Web Server provides diagnostic information about the NK8237 (to
access the NK823x Web Server, see NK823x Web Server [➙ 36]):
In the welcome page, an image of the NK8237 shows an animation
representing the current status of the LEDs (off, on, or blinking).
After login, a detailed list of diagnostic information is available.
If you log in with the Administrator profile, you must click Diagnostic NK to
display the list of diagnostic information.
Available diagnostic information:
Current date and time
Product ID: for example, NK8235
HW version: hardware version, for example NKM8001-A2
HW configuration: hardware configuration, for example 2 serial ports
FW version: firmware version
Add-on information: list of installed add-on components
Linux kernel version
PIC FW version: firmware version of PIC microcontroller (for NKM8001-A2
main board only)
Free RAM
Free memory on SD card/USB MSC: free memory available on the SD card
and (if any) on the USB mass storage device
Branch number: ID assigned to the NK823x in the project configuration
Maintenance and diagnostics