CONFIGURE THE PROTOAIR

6.1

Accessing the ProtoAir Web Configurator

Navigate to the IP Address of the ProtoAir on the local PC using one of two methods:
o
Open a web browser and enter the IP Address of the ProtoAir; the default Ethernet address is
192.168.1.24, the default Wi-Fi Access Point address is 192.168.50.1
If using the FieldServer Toolbox (Section 5.1.1.2), click the Connect button
o
NOTE: If the IP Address of the ProtoAir has been changed, the IP Address can be discovered
using the FS Toolbox utility. See
6.2

Select Field Protocol Configuration

On the Web Configurator page, the first configuration parameter is the Protocol Selector.
Select the configuration desired, using the number key under the Parameter Description header,
and click the Submit button.
o
A message will appear at the top of the screen stating that the update was completed and to
restart the system.
Click the System Restart button on the bottom of the screen and wait for the system to reset.
Appendix A.1

Figure 13: Web Configurator Showing Protocol Selector Parameter

Page 19 of 66
Siemens ProtoAir Start-up Guide
for instructions.