Siemens NK8237 MP4.81-01 Installation Manual page 52

Iec 60870-5-104 gateway for sinteso and cerberus pro fire detection systems
Table of Contents

Advertisement

Configuration
7
Creating the NK8237 Gateway
52
Building Technologies
CPS Fire Safety
Enabling dynamic routing
Configuring the IEC LAN connectivity
1. Select the NK8237 node and expand the subtree.
2. Select the Protocols node.
3. In the toolbar on the left, select the Upstream Protocol icon
 The Upstream generic protocol node is created under the Protocols folder.
By default, the new node is named "Protocol_Upstream".
4. Select the new Upstream Protocol node.
5. Drag-and-drop the selection to the Ethernet node above.
 A link node is created under the Ethernet node.
In the Node tab, no parameters are set.
6. Select the Upstream Protocol link under the Ethernet node.
7. Drag-and-drop the selection to the IEC Master node.
 A link node is created under the IEC Master node.
8. Configure the Master IP Address in the IEC Master Host tab.
9. If necessary, modify the TCP Port Number in the IEC Master Host tab (default
port number is 2404).
(blue/red).
A6V10854379_a_en
30.11.2017