Downloading The Nk8237 - Siemens NK8237 MP4.81-01 Installation Manual

Iec 60870-5-104 gateway for sinteso and cerberus pro fire detection systems
Table of Contents

Advertisement

9.10
Building Technologies
CPS Fire Safety
1. Select the NK8237 node and expand the subtree.
2. In the toolbar on the left, select the Onboard I/O icon
 A new Onboard I/O node appears.
3. Select the new I/O Onboard node.
4. In the toolbar on the left, select the Relay Output icon
 A new Relay Output node appears under the Onboard I/O node.
5. Select the Relay Output node.
6. In the Supervision section of the Node tab, select the Enable supervision check
box.
Configuring the relay output for diagnostic purpose

Downloading the NK8237

Configuration download
The configuration download allows the Composer tool to transfer all the settings to
the NK8237 for runtime use.
Once the NK8237 unit is connected over the IP network, this operation can be
quickly performed from Composer using a right-click command of the NK8237
node.
Firmware download
A firmware download may also be necessary when a new firmware version must
be installed. Unlike the configuration download, the firmware download requires a
software communication infrastructure between the Composer tool and the
NK8237. This is realized based on the standard DMS8000 NS8011 BACnet driver,
which must be added to the Composer project along with the associated DMS8000
station and channel folders. Once this is in place, the NK8237 download can be
performed applying the standard techniques of the NK8000 family (see NK8237
firmware download procedure [➙ 64]).
Standard FTP or secure download
The download can be based on a standard FTP file transfer (available in active or
passive mode) or secured by a dedicated protocol to ensure data privacy (default
download mode).
Configuration
Downloading the NK8237
.
.
A6V10854379_a_en
30.11.2017
7
63

Advertisement

Table of Contents
loading