Private Measurands, Analog Inputs; Private Measurands, Analog Outputs - Siemens SIMEAS P 7KG7750 Manual

Power meter, communication protocol iec 60870-5-103
Hide thumbs Also See for SIMEAS P 7KG7750:
Table of Contents

Advertisement

3.1.2.7

Private Measurands, Analog Inputs

Data Unit = 9
Identifier (max. 2 elements)
Cause of Transmission (COT)
Address of ASDU
Function Type = 130
Information Number = 155
Analog Input 1
Analog Input 2
3.1.2.8
Private Measurands, Analog Outputs (only transmitted, if an Analog Output module is available)
Data Unit = 9
Identifier (max. 2 elements)
Cause of Transmission (COT)
Address of ASDU
Function Type = 130
Information Number = 156
Analog Output Channel 1
Analog Output Channel 2
Note:
Analog Output Channel 1 and Analog Output Channel 2: 0 % = 0 mA; 100 % = 20 mA
Power Meter, SIMEAS P 7KG7750/55, Manual
E50417-B1076-C375-A3, Release 01.2009
Data Mapping
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simeas p 7kg7755

Table of Contents