Siemens SIMEAS P 7KG7750 Manual page 27

Power meter, communication protocol iec 60870-5-103
Hide thumbs Also See for SIMEAS P 7KG7750:
Table of Contents

Advertisement

Figure 3-1 Basic settings - Connection/Transformer Frequency
The SIMEAS P50 automatically recognizes the line frequency (either 50 Hz or 60 Hz)
and can measure it with an accuracy of 10 mHz in the measurement range of 45 Hz
to 65 Hz.
Via IEC 60870-5-103 the deviation of the line frequency is transmitted.
A deviation of 5 Hz corresponds to 100 %.
Examples for 50 Hz nominal frequency:
• Line frequency = 50 Hz → IEC 60870-5-103 value = 0 %
• Line frequency = 54 Hz → IEC 60870-5-103 value = 80 %
• Line frequency = 49 Hz → IEC 60870-5-103 value = -20 %
Examples for 60 Hz nominal frequency:
• Line frequency = 60 Hz → IEC 60870-5-103 value = 0 %
• Line frequency = 64 Hz → IEC 60870-5-103 value = 80 %
• Line frequency = 59 Hz → IEC 60870-5-103 value = -20 %
Note:
If Van is less than 30 % of its nominal value then the frequency is indicated as invalid
in the IEC 60870-5-103 telegram.
Power Meter, SIMEAS P 7KG7750/55, Manual
E50417-B1076-C375-A3, Release 01.2009
Data Mapping
27