4.2
Hardware Interface
Bus connection
9-pole D-SUB outlet
Table 4-1
Protocol
semi-duplex
Max. line length
1000 m / 3300 ft.
Insulation level
AC 500 V
Bus termination
Bus termination via bus plug with integrated terminating resistors.
Figure 4-1 Recommended external termination circuit with open-line fail-safe
Power Meter, SIMEAS P 7KG7750/55, Manual
E50417-B1076-C375-A3, Release 01.2009
Pin
Signal
1
Shield
Shield / Operational ground
2
-
-
3
A
RS485 connection pin A
4
RTS
Directions control
5
GND
Data transmission level (ground towards +5 V
EXT
6
+5 V
Supply voltage for terminating resistors (DC +5 V, max. 100 mA)
EXT
7
-
-
8
B
RS485 connection pin B
9
-
-
Pin assignment of the bus connector (D-SUB outlet)
A
B
Meaning
+5 V
EXT
390 Ohm
220 Ohm
390 Ohm
GND
EXT
Technical Data
)
EXT
43