ABB REL 551 2.3 Series Installation And Comissioning Manual page 51

Line differential protection terminal
Table of Contents

Advertisement

Checking the self supervision signals
,QGLFDWHG UHVXOW
3RVVLEOH UHDVRQ
ADC-module = OK
No problem detected.
ADC-module = Fail
The A/D conversion
module has failed.
Slot04BIM1 = Fail
I/O module has failed.
(Example data, see
following section for
details)
RealTimeClock = OK
No problem detected.
RealTimeClock =
The real time clock has
Warning
been reset.
TimeSync = OK
No problem detected.
TimeSync = Warning
No time synchroniza-
tion.
(QHUJLVLQJ WKH WHUPLQDO
3URSRVHG DFWLRQ
None.
Contact your ABB representative for ser-
vice.
Check that the I/O module has been config-
ured and connected to the IOP1- block.
If the problem persists, contact your ABB
representative for service.
None.
Set the clock.
None.
Check the synchronization source for prob-
lems.
If the problem persists, contact your ABB
representative for service.
&KDSWHU 
45