Making the electrical connections
Where:
1
is ferrules
)LJXUH 
&RQQHFWHG FDEOHV ZLWK IHUUXOHV
If the terminal is equipped with a test-switch of type RTXP 24 Combiflex wires with
20 A sockets must be used to connect the VT circuits and the auxiliary power.
&RQQHFWLQJ WR SURWHFWLYH JURXQG
Connect the unit to the grounding bar of the cubicle with a green/yellow conductor,
cross section at least 1.5 mm
at the back of the terminal.
0DNLQJ WKH VFUHHQ FRQQHFWLRQ
When using screened cables always make sure screens are grounded and connected in
according to applicable engineering methods. This may include checking for appropri-
ate grounding points near the terminal, for instance, in the cubicle and/or near the source
of measuring. Ensure that ground connections are made with short (max. 10 cm) con-
ductors of an adequate cross section, at least 6 mm
tions.
Lc
Rx
Relay
Terminal
Tx
Sc
2
(AWG16), connected to the protective ground connector
2
(AWG10) for single screen connec-
Cc
&KDSWHU 
,QVWDOOLQJ WKH WHUPLQDO
Lc
Tx
External
Equipment
Rx
Sc
en0300087.vsd
29