ABB REL 551 2.3 Series Installation And Comissioning Manual page 113

Line differential protection terminal
Table of Contents

Advertisement



Monitoring of DC analogue
measurements
0RQLWRULQJ RI '& DQDORJXH PHDVXUHPHQWV
A stabilized direct current generator and mA meter with very high accuracy for mea-
surement of direct current is needed in order to test the dc measuring module. The gen-
erator operating range and the measuring range of the mA meter must be at least
between -25 and 25 mA.
Prepare the terminal for verification of settings as outlined in section "Preparing for
test" in this chapter. Connect the current generator and mA meter to the direct current
input channels to be tested.
9HULI\LQJ WKH VHWWLQJV
3URFHGXUH

&RQVLGHU WKH QHHG WR EORFN RXWSXW VLJQDOV

&KHFN WKDW WKH YDOXHV SUHVHQWHG RQ WKH +0, PRGXOH FRUUH
VSRQGV WR WKH PDJQLWXGH RI LQSXW GLUHFW FXUUHQW ZLWKLQ WKH OLP
LWV RI GHFODUHG DFFXUDF\
The service value is available under the submenu:
6HUYLFH 5HSRUW,26ORWQP0,0[0,[\9DOXH
where:
QP
represents the serial number of a slot with tested mA input module
[
represents the serial number of a mA input module in a terminal
\
represents the serial number of a measuring channel on module x.

&KHFN WKH RSHUDWLRQ RI $'%6 RU ,'%6 IXQFWLRQ ZKHQ DSSOLFD
EOH &RPSDUH ZLWK WKH H[SHFWHG YDOXHV
The operation of ADBS or IDBS function can be checked sepa-
rately with the setting of RepInt = 0. The value on the HMI must
change only when the changes in input current (compared to the
present value) are higher than the set value for the selected dead
band.
&KDSWHU 
9HULI\LQJ VHWWLQJV E\ VHFRQGDU\
LQMHFWLRQ
107