Line differential protection (DIFL)
7HVW7HVW0RGH'LVWXUE5HSRUW

$FWLYDWH WKH WULS E\ VHWWLQJ 5HOHDVH ORFDO
This command is found in the menu under:
7HVW7HVW0RGH'LIIHUHQWLDO
This command must be saved in order to be activated. Observe that
the command 5HOHDVH/RFDO will allow the trip outputs to be acti-
vated during the tests.

,QMHFW D FXUUHQW LQ / DQG LQFUHDVH WKH FXUUHQW XQWLO RSHUDWLRQ
LQ SKDVH / DQG / WDNHV SODFH
The injected operation value must correspond to the set IMinOp·
Ir·CTFactor. This value is to be read as IDiffL1 and IDiffL2, and
50% of IDiffL1 as IBiasL1 and IBiasL2. The IDiffL3 should be
zero and IBiasL3 25% of IDiffL1. These values are read on the
HMI under:
6HUYLFH 5HSRUW)XQFWLRQV'LIIHUHQWLDO'LII 9DOXHV

5HSHDW VWHS

IRU SKDVH / DQG /
The result shall be transposed one, respectively two steps.

,QMHFW D V\PPHWULFDO WKUHHSKDVH FXUUHQW DQG LQFUHDVH WKH
FXUUHQW XQWLO RSHUDWLRQ LV DFKLHYHG LQ DOO WKUHH SKDVHV
The IMinOp·Ir·CTFactor value shall be obtained for operation and
read for I
in all three phases. 100% of I
Diff
in all three phases.

5HDG WKH WUDQVPLVVLRQ GHOD\ RQ WKH +0,
This command is found in the menu under:
6HUYLFH YDOXH)XQFWLRQV'LIIHUHQWLDO'LII&RP&RP,QIR
This delay is not allowed to exceed 12 ms.
9HULI\LQJ VHWWLQJV E\ VHFRQGDU\
shall be read for I
Diff
Bias
&KDSWHU 
LQMHFWLRQ
101