FA - 28 PID shutdown operation
0: stop without calculation.
1: stop operation.
Use to select whether the PID will continue to operate under the shutdown state of the PID. In general
applications, PID should the operation should be stopped.
FA - 29 pressure sleep option
0: the frequency inverter sleeps and wakes up according to the frequency node according to the functions of F8 -
14 ~ F8 - 17.
1: the frequency inverter sleeps and wakes up according to the pressure node according to the functions of FA -
30 ~ FA - 33.
FA - 30 wake-up pressure percentage
FA - 31 wake-up pressure delay time
Wake up pressure percent = (wake up pressure / target pressure) X 100 %.
When the feedback pressure is less than the wake-up pressure, it will enter the wake-up state after FA - 31
times.
FA - 32 sleep pressure percentage
FA - 33 sleep pressure delay time
Sleep pressure percentage = (sleep pressure / target pressure) X 100 %.
When the feedback pressure is greater than the sleep pressure, it will enter the sleep state.
Note: during sleep, the operation indicator on the control panel flashes for 1s cycle.
HV610 can switch operation between two motors. The two motors can respectively set motor nameplate
parameters and can respectively enter Line motor parameter tuning, VF control or vector control can be selected
separately, encoder related parameters can be set separately, and parameters related to VF control or vector control
performance can be set separately.
The Fb group function code corresponds to all parameters of the motor 2 and FB group. Its content definition
and usage method are consistent with those of the first motor. This will not be repeated here. The user can refer to
the description of the relevant parameters of the first motor. The specific FB - 00 ~ FB - 37 refers to f1 - 00 ~ f1 - 37
group parameters, and FB - 38 ~ FB - 55 refers to F2 - 00 ~ F2 - 17 parameters.
FB - 61 2nd motor control mode
When the motor is selected as the second motor, the control mode takes effect, and the definitions of 0 ~ 2 are
the same as F0 - 01.
0: no PG open loop vector control
1: PG closed loop vector control
2:V/F
FB - 62 second motor acceleration and deceleration time
selection
0: the acceleration and deceleration time is the same as that of the first motor.
1: the first group of acceleration and deceleration time
0~1【0】
0~1【0】
0.0~100.0%【80.0%】
0~6000.0【1.0】
50.0~1000.0%【80.0%】
0~6000.0【60.0】
FB group 2 motor parameters
0~2【0】
0~4【0】