Constant Pressure Control Solution Case V0.1 For Water Pump And Fan - HNC Electric HV610 Series User Manual

Table of Contents

Advertisement

Constant pressure control solution Case V0.1 for water pump and fan

1.1. Overview
The process PID closed-loop control regulates the rotation speed of the motor and indirectly controls the water
pressure or air pressure of the pipeline to be constant.
2.1 Two types of pressure sensors for pump and fan control
Type 1: 0 ~ 10v remote pressure gauge
Type 2: 4 ~ 20ma pressure transmitter
3.1 Control wiring diagram
Type 1: pressure sensor is 0 ~ 10v remote pressure gauge
Type 2: the pressure sensor is a 4 ~ 20mA
Pressure transmitter
3.2 Setting parameters
Type 1: 0 ~ 10v remote transmission pressure gauge
Name
Control mode
Main frequency source
PID given source
Remote transmission pressure gauge signal 0 ~ 10v
Forward run
Reverse run
Pressure transmitter 4 ~ 20mA
Note: the control board AI2 jumper is shorted to the current input side
Forward run
Reverse run
Function code
Numerical
F0-01
2
F0-03
8
FA-00
0
V/F control
PID constant pressure water supply
Pressure setting is set by FA - 01 parameter
170