8-4-3

List of Device Events and Troubleshooting

The list of registered device events and corrections is as below.
IO-Link
event
Event name
torFDT display
code
5000
Hardware
Error Appeared:
hex
Error
Device hardware
fault
5111
Unit/Input
Warning Ap-
hex
Power Sup-
peared:
ply Voltage
Primary supply
Drop
voltage under-run
6320
Service Da-
Error Appeared:
hex
ta Error
Parameter error
7701
I/O Cable
Error Appeared:
hex
Disconnec-
Wire break of sub-
tion
ordinate device 1
7710
I/O Cable
Error Appeared:
hex
Short-circuit
Short circuit
8CB0
Output Pow-
Warning Ap-
hex
er Supply
peared:
Voltage
Secondary supply
Drop
voltage fault
8DFE
Non-volatile
Warning Ap-
hex
Memory
peared:
Write Error
Non-volatile Mem-
ory Write Error
*1.
Appears in Value of Detailed Device Status.
NXR-series IO-Link I/O Hub User's Manual (W620)
CX-Configura-
Type
*1
Error
Warn-
ing
Error
Error
Error
Warn-
ing
Warn-
ing
Description
The Non-volatile Mem-
Cycle the Unit/input power supply to the
ory Hardware Error was
IO-Link I/O Hub. If this error persists af-
detected.
ter you cycle the power supply, replace
the IO-Link I/O Hub.
The Unit/input power
Check if the Unit/input power is sup-
supply voltage is low.
plied. If it is supplied, check if the power
supply voltage is not below the specifi-
cation.
The power supply to
Download the setting parameters for
the IO-Link I/O Hub
the IO-Link I/O Hub again. Do not inter-
was interrupted while
rupt the power supply to the IO-Link I/O
writing of the setting
Hub or communications with CX-Con-
parameters for the IO-
figuratorFDT during download.
Link I/O Hub. Alterna-
tively, communications
with CX-Configura-
torFDT were interrupt-
ed.
The I/O cable is bro-
Check the wiring of the I/O cable.
ken.
There is a short-circuit
Check the wiring of the I/O cable.
in the I/O cable.
The output power sup-
Check if the output power is supplied. If
ply voltage is low.
it is supplied, check the following:
If it is supplied, check if the power sup-
ply voltage is not below the specifica-
tion.
Failed to write to the
Download the setting parameters for
non-volatile memory.
the IO-Link I/O Hub again. If the prob-
lem persists after you download the set-
ting parameters, replace the IO-Link I/O
Hub.
8 Troubleshooting
Correction
Pin 2 of the IO-Link Master Unit port
is in SIO (DO) Mode and ON
8