3 Installation

3.1 Delivery

The heat pump is delivered ready to install, i.e.
electrically pre-wired, on a one-way palette and
packed in foil. The cladding is packaged extra.
Report any transport damage immedi-
ately on receiving the heat pump!

3.2 Transport

The heat pump is to be stored and transported
packaged up. Careful transport at an angle up to
45° is permitted over short distances. Ambient
temperatures from –20°C to +45°C are permitted
both for transport and storage. The standard pack-
aging offers no weather or seawater protection.
Transport damage can only be recognised if this is
made known to the driver of the delivery vehicle
during, or immediately after unloading.

3.3 Tilting dimensions of indoor unit

The tilting dimension of the heat pump is 209cm:
Fig. 2: Titling dimension of the heat pump

3.4 Select the place of instillation

The heat pump TERRA can be installed in any dry
and frost free room. Installation must take place
on an even, horizontal surface.
BA OCHSNER AQUA TERRA_EN_V01.1.docx
Placement of the unit should be such that servic-
ing and maintenance are possible.
2090 mm
The heat pump must be acoustically de-coupled
from the floor. Reverberant rooms can lead to in-
creased noise sensitivity A possible transfer of
noise to adjacent rooms cannot be ruled out and
should be considered when planning the system.
Fig. 3: Minimum clearances