HIGH EFFICIENCY AIR/WATER HEAT PUMPS OPERATING MANUAL ► AIR FALCON 212 TRANSLATION OF THE ORIGINAL MANUAL VALID FROM OTS APP SOFTWARE VERSION V03.02.XXX...
Appliance reset 11.4.1 Setting seasonal operation 21.4 Re-inputting available elements 11.5 Weather-compensated controller 21.5 System lockout 11.5.1 Heating curve 21.5.1 Emergency mode 11.5.2 Cooling curve 21.5.2 System failure 11.6 Enabling heating/cooling 21.6 Reporting errors and faults www.ochsner.com | BA-982018-AIR FALCON-ih-EN...
Page 3
Adjusting silent mode Cascade 31.1 Visualisation on user interface Factory settings Function expansion through auxiliary modules 72 33.1 DHW circulation pump 33.1.1 Return temperature 33.2 Pool heating system 33.2.1 Operating program 33.2.2 Parameters 33.2.3 Operating data BA-982018-AIR FALCON-ih-EN | www.ochsner.com...
The latest version of the operating manual can be found on the OCHSNER ► We recommend an annual inspection (to assess the homepage in the download area.
Only qualified contractors may open the appliance. Low flammability ► Commissioning of the appliance may be carried out only by OCHSNER Customer Service or by customer service partners authorised by OCHSNER. BA-982018-AIR FALCON-sh-EN | www.ochsner.com...
Page 6
Protect the appliance from dust and dirt during build- ing work. ► Alterations to the appliance may only be carried out by OCHSNER Customer Service or by customer ser- vice partners authorised by OCHSNER. ► Functions to protect the heat pump can be enabled using the controller.
The outdoor air is routed through the outdoor unit by means of a fan. The indoor and outdoor units are connected through refrigerant lines. Due to the defrosting function integrated into OCHSNER air/water heat pumps, the system also operates flawlessly at temperatures below -15°C.
Page 9
How split systems work 00_400_200_202_01_split_Funktionsweise-EN | www.ochsner.com...
► 17 Shut-off valve 18 Fill and drain stopcock Indoor unit hydraulics Appliance components The system must be engineered using an OCHSNER standard hydraulic schematic or an OCHSNER special 4.3.1 Indoor unit hydraulic system. The indoor unit is intended to be installed inside the build- ing only.
Increasing the room temperature by 1°C results in The following maintenance work may be carried an increase in consumption of 5-7%. out only by OCHSNER Customer Service or by an authorised OCHSNER Customer Service partner: Ventilation - Maintenance work not described in the section...
(WNA) and if necessary the heat source system » (WQA) using the flow meters specified by OCHSNER. Ensure that the safety valve is closed again after the test. When non-routine work takes place that requires refilling (e.g.
Standard settings for the controller are set by OCHSNER Customer Service as part of the 7.2.1 Resetting the high limit safety cut-out commissioning process. The system user and their...
This way, safety functions such as frost protection remain active. Material damage If the power supply to the heat pump system is interrupted and there is a risk of frost, drain the system on the water side. BA-982018-AIR FALCON-ba-EN | www.ochsner.com...
The main screen shows current temperatures and the sta- tus of the heat pump. There is a separate main screen for each heating circuit and each DHW circuit. Swipe side- ways on the touchscreen to switch between the individual circuits. www.ochsner.com | OTS_EN...
(heat pump, electric immersion heater, boiler, etc.) has its own submenu. 9.3.8 Current DHW temperature In addition to the current heating circuit temperature, the current temperature of the DHW circuit is also displayed in the heating circuit. 1 Circuit identifier 2 Name OTS_EN | www.ochsner.com...
Complete the registration form. Material damage After successful registration, you will receive a confirma- The OTS app is available from OCHSNER in the tion email. “Google Play Store” and “App Store”. Apps from the “Google Play Store” and “App Store” undergo »...
» ways delayed. Press the plus or minus button to adjust the “Target » Perform only one adjustment per day. room temperature”. OTS_EN | www.ochsner.com...
The temperature is always regulated to the reduced target value. The Comfort program is the default operating program of the heating circuit. In this mode, a time program can be used. (See page 35, Time program) www.ochsner.com | OTS_EN...
(See page 23, Weather-compensated controller) reduced cool- cooling mode: Target room temperature standard cool- Note A change in the target room temperatures also Target room temperature reduced cooling changes the energy consumption of the heat pump system. OTS_EN | www.ochsner.com...
Only cooling Only cooling mode is enabled. There is no heating. enabled Control takes place in accordance with the set cooling curve. This setting prevents heating mode from starting up, for example on a cold summer day. www.ochsner.com | OTS_EN...
8 Heating curve calculated by controller (applicable when target room temperature is less than heating curve reference room temperature) 9 Heating function active 10 Heating function not active OTS_EN | www.ochsner.com...
Page 24
» Enter the initial setting values in the modification list. (See page 25, Modification list) » Return to the main screen. Version 2: There is no required heating curve from a pre- vious heating system. www.ochsner.com | OTS_EN...
Page 25
Modification list Date Flow temper- Flow tem- Heating limit Outdoor tem- Standard Heating curve Comments ature at base perature at perature base outdoor tem- reference point standard point perature room temper- outdoor tem- ature perature Initial setting OTS_EN | www.ochsner.com...
9 Cooling curve calculated by controller (applicable when target room temperature is less than cooling curve reference room temperature) 10 Cooling function active 11 Cooling function not active www.ochsner.com | OTS_EN...
Page 27
Select the heating circuit for which you want to make ways delayed. a change. » Perform only one adjustment per day. » Select “Cooling curve”. Version 1: There is a required cooling curve from a previ- ous heating system. OTS_EN | www.ochsner.com...
Page 28
Modification list Date Flow temper- Flow tem- Cooling limit Outdoor tem- Standard Cooling Comments ature at base perature at perature base outdoor tem- curve refer- point standard point perature ence room outdoor tem- temperature perature Initial setting www.ochsner.com | OTS_EN...
The temperature is regulated to the perature sensor. target value: Target room temperature standard heating » If you want room temperature compensation, contact your system partner or switch to expert mode. OTS_EN | www.ochsner.com...
Mixing valve heat- If the opening degree of the mixing » ing circuit closed valve is reduced, then ON is displayed Press the plus or minus button to adjust the target here. DHW temperature. www.ochsner.com | OTS_EN...
DHW. The modified mixing ratio produces a larger DHW ca- pacity. 12.2.1 Setting the operating program Via the main screen, you can choose between the following operating programs for each DHW circuit. ► OTS_EN | www.ochsner.com...
The temperature is regulated to the target value: Target value for Eco The switching differentials can be changed via the menu. The DHW temperature falls below the tar- » get value by the value set here. Open the menu. www.ochsner.com | OTS_EN...
3 Current temperature at temperature sensor In order to save energy, we recommend that an- 4 Heat demand ti-legionella mode is coordinated with the time program for DHW mode. (See page 37, Example of a DHW time program) OTS_EN | www.ochsner.com...
Charge abort- There is a charging shutdown. used, the DHW heat input must be adjust- ed for optimum operation. This parameter is set by OCHSNER Customer Service Priority mode There is a smart grid demand. The heat during commissioning. pump is in the following mode: Priority mode www.ochsner.com | OTS_EN...
DHW circuit are set at the factory so that the sys- tem always heats to the respective standard value. 1 Time program Note For heating circuits, a time program is only possible in the following operating program: “Comfort” (See page 20, Operating program) OTS_EN | www.ochsner.com...
Page 36
Reduced target The switching times between the standard value target value and reduced target value can be set individually for each day. The tem- perature is regulated to the reduced target value in the blue area. www.ochsner.com | OTS_EN...
Time program 13.1.1 Example of a DHW time program 1 Reduced target value 2 Standard target value 3 Anti-legionella mode target value A Monday B Tuesday C Wednesday D Thursday E Friday F Saturday G Sunday OTS_EN | www.ochsner.com...
The activity of the electric auxiliary heater has the 14.3 Operating data option to be shown on the heat pump display. » Inform OCHSNER Customer Service during 14.3.1 Electric auxiliary heater internal commissioning if you require this optional ver- sion (CH).
If the bivalent point is set too low, the heat pump may not reach the required temperatures for DHW and heating. » Only make changes to this parameter in con- sultation with your system partner. OTS_EN | www.ochsner.com...
Smart Grid energy tariffs. Priority mode Parameters Description Unit Association Forced draw-off (BWP) Electricity tariff shutdown DHW temper- In DHW mode, the temperature is regulat- °C ature: ed to the target value set here. Target value for Priority mode www.ochsner.com | OTS_EN...
(See page 33, Anti-legionella mode) ► Target room temperature decrease 16.5 Buffer tank ► Buffer tank target temperature reduction for forced draw-off If a buffer tank has been installed, this is also taken into account in SmartGrid mode. OTS_EN | www.ochsner.com...
Calculation method Up to V03.00.xxx The electrical energy consumption of the heat pump is made up purely of the electrical ener- 17.1.1 Viewing operating data gy consumption of the inverter. » Open the menu. » Select “Heat management”. www.ochsner.com | OTS_EN...
Hours of opera- This indicates the absolute hours of op- tion: DHW tank eration of the electric auxiliary heater in auxiliary heater the DHW tank if one has been installed. EHWP Electrical energy consumption, heat pump, heating OTS_EN | www.ochsner.com...
Display on the heat pump Modbus communication is activated during commissioning If a building management system is used for control, all by OCHSNER customer service or by a customer service standard main screens are no longer displayed. Only es- partner authorised by OCHSNER.
3-way tractor. Standard settings for the controller are set switching module for by OCHSNER Customer Service as part of the heating/DHW, mix- commissioning process. The system user and their ing valve service partner are responsible for any further cor- [#11.4]...
Page 46
Contact service Service temperature partner partner [#72.1] Relative humidity Contact service Service heating circuit 1 partner partner [#39] Compressor motor Contact service Service protection partner partner [#72.2] Relative humidity Contact service Service heating circuit 2 partner partner www.ochsner.com | OTS_EN...
Communication, Contact service Service » heat pump 3 partner partner Select “Acknowledge error”. [#100.4] Communication, Contact service Service » heat pump 4 partner partner Acknowledge the fault. [#101] Maximum pressure Contact service Service ratio (envelope) partner partner OTS_EN | www.ochsner.com...
The electric auxiliary heater runs to cover the heating/ This setting remains active for 7 DHW load. days. The setting is then reset. To continue to use this operating program, you must confirm the information about emergency mode again. www.ochsner.com | OTS_EN...
No heat is generated. 22. Data connection to cloud Procedure The device is connected to the OCHSNER Cloud via the » internet. You can deactivate this connection. Contact your Contact your service partner.
Here, you can remove users and assign administration rights. Adding users » On the system overview, under the relevant system, select “Invite” to add a new user. 23.3 Changing user data » Select “Menu”. » Select “Account”. www.ochsner.com | OTS_EN...
Select “Company information”. 5 The commissioning date is displayed here. This is entered by OCHSNER Customer Service during commissioning. 26. Software updates 6 You can set the required time zone in this menu.
Only the first two sections are relevant for op- pending on how it is operated. It is therefore not eration: possible for OCHSNER to provide an estimate. If the data volume is too low and it is exceeded, this Software ver-...
The value set here must be within the A = B < C - D heat pump‘s limits of use. Radiator heat- E = B > C - D/2 ing is not possible with every heat pump. OTS_EN | www.ochsner.com...
Page 54
If the set heating curve and the room temperature compen- factor Kp”is set to 0, no room temperature com- sation result in a target flow temperature that is lower than pensation will take place. the room temperature, then the target flow temperature www.ochsner.com | OTS_EN...
1 Cooling limit 2 Switch-ON differential cooling limit 3 Average outdoor temperature 27.2.3 Heating curve 4 Cooling is enabled In addition to the standard settings for the heating curve, other settings are also possible in expert mode. OTS_EN | www.ochsner.com...
WARNING: Incorrectly setting the “Tank sensor offset” may cause the DHW temperature to fall below 60°C in anti-legionella mode, resulting in the formation of legionella bacteria. www.ochsner.com | OTS_EN...
The actual value is still above the target value. The compressor stops. A Compressor OFF B Compressor ON C Target value D Actual value E Output demand T = Temperature P = Compressor output t = Time OTS_EN | www.ochsner.com...
2 Set target buffer tank temperature ► If the buffer tank temperature is too low, condensate 3 Actual buffer tank temperature may start to form on the buffer tank due to humidity. This leads to a risk of mould formation. www.ochsner.com | OTS_EN...
This indicates the electrical EHWP consumption, heat energy consumed in the de- » pump, heating fined period by the heat pump Select “Settings”. for heating. The parameters can be found under the following menu item: “Buffer tank temperature limit” OTS_EN | www.ochsner.com...
The increase values can be set via the menu. DHW heating. » Open the menu. » Select the heating circuit for which you want to make a change. www.ochsner.com | OTS_EN...
The heat pump is in cooling mode draw-off Select “Operating program”. Smart Grid is in the Forced draw-off op- » erating mode Select “Operating program heating circuit”. » The increase/decrease can be adjusted via the menu. Select “OFF”. OTS_EN | www.ochsner.com...
If the target value is not reached, the target temperature remains unchanged until it is achieved. Only then will the program continue. This can extend the screed drying program. www.ochsner.com | OTS_EN...
If there are test phases where the target value is not reached, this can extend the screed drying program con- siderably. Status of The current phase of the screed drying screed drying program is shown here. program OTS_EN | www.ochsner.com...
The status for the relay test can be set » ing circuit here. Select “Alarms” Inactive The relay test is not active. Control takes place automatically. All actuators are switched off. Mixing valve The heating circuit mixing valve is being opening opened. www.ochsner.com | OTS_EN...
This priori- service life here. tisation is standard. If you would prefer a different prioritisation, please contact your service partner. The DHW circulation pump is switched on and off via these two parameters. www.ochsner.com | BA-982018-AIR FALCON-OTS-EN...
The heat pump is in the following oper- ating program: “Manual heating” This operating program can only be set 29.2.1 Viewing operating data by OCHSNER Customer Service and should only be used for testing purpos- » Open the menu. Manual cool- The heat pump is in the following oper- »...
» Create and move the changeover points to adapt “Si- lent mode” to your personal requirements. » Save the changes you make. www.ochsner.com | BA-982018-AIR FALCON-OTS-EN...
The master heat pump and the controlled heat pumps are set during commissioning by OCHSNER customer service or by a customer service partner authorised by OCHSNER. 31.1 Visualisation on user interface In the case of the master heat pump, visualisation on the user interface is the same as for an individual system.
Factory settings 32. Factory settings Parameters Unit AIR FALCON 212 Target room temperature °C standard heating Target room temperature re- °C duced heating Target room temperature °C standard cooling Target room temperature re- °C duced cooling Heating limit °C Outdoor temperature base °C...
Page 71
Factory settings Parameters Unit AIR FALCON 212 Room temperature compen- sation correction factor Kp Room temperature average calculation period Switching differential ON - room too cold Switching differential OFF - room too warm Switching differential ON - room too warm...
The runtime of the DHW circulation pump has been » reached: Open the menu. » Select the DHW circuit for which you want to adjust the DHW circulation pump setting. » Select “Settings”. » Make the required settings. www.ochsner.com | OTS_ZSM_EN...
You must be in expert mode to use this function. Parameters Description Unit Pool flow tem- A flow temperature can be set for the °C perature pool heating system. This should be 10 K higher than the required pool tempera- ture. OTS_ZSM_EN | www.ochsner.com...
Page 74
Minimum runt- Here, you set the minimum time the auxiliary energy generator must run after switching on. Minimum Here, you set the minimum time the auxil- standby time iary energy generator must stand by after being switched off. www.ochsner.com | OTS_ZSM_EN...
Page 75
“Bivalent point”, a temperature window is cre- » ated in which no heating takes place. Return to the main screen. » Do not set the “Heat pump bivalent point” higher than the “Bivalent point”. OTS_ZSM_EN | www.ochsner.com...
Page 76
Hours of oper- This indicates the hours that the OTS More detailed information about the relay test can be found ation controller requested the auxiliary energy in the relevant section. (See page 64, Relay test) generator for DHW mode. www.ochsner.com | OTS_ZSM_EN...
Page 78
ERP DATA GENERAL AIR FALCON 212 C11A M1-5 AIR FALCON 212 C11B M1-5 Low temperature heat pump: With auxiliary heating appliance: Combination heater with heat pump: TEMPERATURE APPLICATION: LOW / CLIMATIC CON- AIR FALCON 212 C11A AIR FALCON 212 C11B...
Page 79
TEMPERATURE APPLICATION: LOW / CLIMATIC CON- AIR FALCON 212 C11A AIR FALCON 212 C11B DITIONS: COLDER M1-5 M1-5 Combination heater: DHW heating energy efficiency [ηwh] TEMPERATURE APPLICATION: MEDIUM / CLIMATIC AIR FALCON 212 C11A AIR FALCON 212 C11B...
Page 80
TEMPERATURE APPLICATION: LOW / CLIMATIC CON- AIR FALCON 212 C11A AIR FALCON 212 C11B DITIONS: AVERAGE M1-5 M1-5 Nominal heating output [P rated] (for heating appliances and combination heaters with heat pump, the nominal heating output P rated is equal to the design load in heating mode Pdesignh) Specified output for partial load [Pdh]: Outdoor air temperature [Tj]=-7°C /...
Page 81
TEMPERATURE APPLICATION: MEDIUM / CLIMATIC AIR FALCON 212 C11A AIR FALCON 212 C11B CONDITIONS: AVERAGE M1-5 M1-5 Specified output for partial load [Pdh]: Outdoor air temperature [Tj]=Tbiv / 7.08 7.08 Indoor air temperature=20°C Specified output for partial load [Pdh]: Outdoor air temperature [Tj]=TOL / 5.30...
Page 82
TEMPERATURE APPLICATION: LOW / CLIMATIC CON- AIR FALCON 212 C11A AIR FALCON 212 C11B DITIONS: WARMER M1-5 M1-5 Outdoor sound power level [LWA] dB(A) Annual energy consumption [QHE] 1,636 1,636 Combination heater: Specified load profile Combination heater: Daily power consumption [Qelec] Seasonal central heating energy efficiency [ηs]...
Page 83
TEMPERATURE APPLICATION: MEDIUM / CLIMATIC AIR FALCON 212 C11A AIR FALCON 212 C11B CONDITIONS: WARMER M1-5 M1-5 Specified COP for partial load [COPd]: Outdoor air temperature [Tj]=TOL / 1.54 1.54 Indoor air temperature=20°C Operating limit temperature [TOL] °C Limit for heating water operating temperature [WTOL] °C...
Page 84
Kyoto Protocol. R32 refrigerant must not be discharged into the atmosphere. Note The refrigerant used is assigned to safety class A2L. It is not harmful to the environment and is of low flammability. www.ochsner.com | BA-982018-AIR FALCON-EN07...