Led Colors And Patterns - Siemens QAM2151.040/MO Basic Documentation

Duct temperature, humidity and air quality sensors, immersion temperature sensor, modbus rtu (rs-485)
Table of Contents

Advertisement

4.4 LED colors and patterns

A6V11610643_en--_a
Holding
Description
Register
(16-bit)
No.
765
Baud rate
766
Transmission format
(start bits-data bits-
parity-stop bits)
767
Reserve
768
Bus configuration
command
NOTES:
The register number is counted from 1.
764 (Modbus address) cannot be configured as 246 via a master. Address 246
is reserved for on-event addressing.
In the case of a multiple writing command from the master with invalid values,
the sensor rejects the command with an error notice. The register values
remain unchanged.
Bus configuration command (768) is for on-event addressing only.
Software version format: major version is 1 byte, minor version is 1 byte and
build version is 2 bytes, such as [2.01.33] = 0x02010021.
Color
Pattern
Green
Constant until device boots
Flashing (1 s on / 5 s off)
Flickering
Orange
Flashing (1 s on / 5 s off)
Flashing (1 s on / 1 s off)
Constant
Red
Flashing (0.1 s on / 1 s off)
Flashing (1 s on / 5 s off)
Range
Unit
Scaling
0 = Auto
-
-
1 = 9600bps
2 = 19200bps
3 = 38400bps
4 = 57600bps
5 = 76800bps
6 = 115200bps
0 = 1-8-E-1
-
-
1 = 1-8-O-1
2 = 1-8-N-1
3 = 1-8-N-2
-
-
-
0 = Ready
-
-
1 = Load
2 = Discard
Description
Power up
Power-up is completed.
Working properly
Modbus is configured.
Bus communication
Bus communication failure
Power-up is completed.
Working properly
Modbus is not configured.
Waiting configuration via Modbus in on-event
addressing mode
Invalid parameter value received from master
Internal error:
Sensing element malfunction
Sensing element is not connected.
Configurations
LED colors and patterns
Default
R/W
0
RW
0
RW
-
RW
0
RW
4
9 | 16

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents