Push Button Configuration; On-Event Addressing (Climatix Tm Controllers Configuration) - Siemens QAM2151.040/MO Basic Documentation

Duct temperature, humidity and air quality sensors, immersion temperature sensor, modbus rtu (rs-485)
Table of Contents

Advertisement

Configurations
4

Push button configuration

4.5 Push button configuration
Push button
4.5.1 On-event addressing (Climatix
Enter addressing mode
and configuration workflow
via push button
10 | 16
When DIP2-Position 7 is OFF (default setting), push button function is activated.
The following can be operated via push button:
On-event addressing
Resetting the Modbus parameters to factory default settings
On-event addressing is a rapid configuration approach working together with
Siemens Climatix
controllers.
TM
The sensor is wired and connected to the Climatix
Press the
LED
push
button for
1...5 s
Constant red
5...10 s
LED off
< 10 min
Constant orange
in addressing
mode
controllers configuration)
TM
Action
Press and hold the button
Release the button
Press once and release the
button
controller via Modbus.
TM
More details
Entering the addressing mode, LED is
constant orange.
Address is set to 246 temporarily.
Baud rate is set to Auto and then
auto baud rate recognition is
done.
Format is set to 1-8-E-1
temporarily.
Communication is established.
Master writes the Modbus
parameters.
1)
Master writes "1" into register
4x0768 ("Bus configuration.
command") to activate the
change.
After a successful pairing, the LED
flashes green (1 s on / 5 s off).
Otherwise the LED turns back to its
original state.
Time out after 30 s
2)
If the LED is constant orange, a short
press of the push button stops and
exits the on-event addressing mode.
After exiting addressing mode, the
LED turns back to its original state.