Network - socomec ATyS t Instruction Manual

Automatic transfer switching equipment
Hide thumbs Also See for ATyS t:
Table of Contents

Advertisement

≤630ABOTTOM VIEW
1/2
3/4
5/6
1/2
3/4
5/6
7/8
5/6
3/4
7/8
5/6
3/4

7.4.3. Network

Power inputs (terminals 101-102 & 201-202) are 220/240/277 VAC (208 - 277 VAC) ± 20%. It is necessary to adapt the
power input cable connections according to the network configuration. (Power supply to be taken between phase to phase
or between phase and neutral).
Verify that the power supply between terminals 101 – 102 and 201 – 202 (nominal auxiliary
CAUTION
voltage supply) is within 208-277 VAC ± 20%.
• Standard kit:
Network 380/415 VAC ± 20% with neutral
conductor (no kit modification required):
Red wires
mechanical
B
A
7/8
5/6
3/4
1/2
L/N N/L
ATYS t - 541995C - SOCOMEC
7/8
7/8
Red wires
1/2
B
A
mechanical
cables support
1/2
L/N N/L
Black wires
B
A
cables
support
L/N
N/L
7/8
5/6
3/4
≥800ABOTTOM VIEW
1/2
3/4
1/2
3/4
Black wires
7/8
B
A
L/N
N/L
7/8
• Kit Modification:
For network 220/240 VAC ± 20%, power supply
cables A-B to connect between phases
Red wires
B
7/8
5/6
3/4
1/2
1/2
5/6
7/8
5/6
7/8
5/6
3/4
1/2
5/6
3/4
1/2
Black wires
mechanical
A
B
A
cables
support
L/N N/L
L/N
N/L
7/8
5/6
3/4
1/2
47
EN