Power supply
Nominal value
Tolerance
Residual ripple
Pin 1: electronics
(and CP sensors)
Pin 2: valves
(and CP outputs)
Protection against
electric shock
Electrical isolation
Field bus interface opto−uncoupled from the power supply
connection
Power supply: pin 1 electrically isolated from pin 2
26
24 V DC (protected against incorrect
polarity, fused internally, automatic restart)
21.6 ... 26.4 V
4 Vpp (within tolerance)
Current consumption: max. 200 mA
+ current consumption of the sensors
Current consumption: sum of all
switched−on CP solenoid valves (see man
ual CP pneumatics") and CPI/CP outputs
(if not with their own power supply)
By the use of PELV current circuits
(protection against direct and indirect
contact as per IEC/DIN EN 60204−1)