E-Stop Safety Modules with Adjustable Delay –
The same screwdriver is handy
for turning the rotary Delay Time
selector switches and for setting
the DIP switches.
Figure 5. Use a screwdriver to gently pry
the cover loose from the Module
housing.
DIP AND SELECTOR SWITCH SETTINGS
(REMOVE COVER, FACTORY SETTINGS SHOWN)
DELAY OFF TIME FOR CONTACTS
57 - 58, 67 - 68, 77 - 78, 01 - 02, 87 - 88
0
0 = 0s
5 = 6s
9
1
1 = 0.5s
6 = 8s
8
2
8
2 = 1s
7 = 10s
7
3
7
3 = 2s
8 = 15s
6 5
4
4 = 4s
9 = 20s
SWITCHES MUST MATCH
TO OBTAIN DESIRED DELAY TIME.
S1
S2 S3
S4
S1.1S2.1 S3.1 S4.1
1
1
1
1
1
1
0
0
0
0
0
0
S1
S1.1 S2 S2.1 S3 S3.1 S4 S4.1
AUTO RESET
1
1
MANUAL
0
0
RESET
2 CHANNEL
1
1
FEEDBACK
1 CHANNEL
0
0
FEEDBACK
AUTO
1
POWER UP
MANUAL
0
POWER UP
1 CH. INPUT
2 CH. INPUT
Figure 6. Module DIP switches and
selectors, set to factory settings
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
The DIP switches and selector switches are located inside the Module housing, behind
the front plate. Before adjusting any settings, turn OFF power to the Module. Remove
the front plate by using a screwdriver in the slot on the right side and gently prying the
cover away from the housing (Figure 5). Turn the rotary Delay Time selector switches
to the desired position using the same small screwdriver in the slot on the arrow. Use
the screwdriver blade to slide the DIP switches to their proper positions also.
The corresponding pairs of DIP switches and the two rotary Delay Time selector
switches must match at all times, or a Fault condition will result. (If this occurs, turn
the power OFF, adjust the pairs of switches to match, and turn the power supply back
ON.) Figure 6 shows the DIP switches and Delay Time selector switches properly set
for No Delay, Manual Reset, 1-Channel Monitoring, Manual Power-Up, and 2-Channel
Input.
The E-Stop Safety Module factory settings are as follows:
Manual/Auto Reset (S1, S1.1)
1-/2-Channel Monitoring (S2, S2.1)
Manual/Auto Power-Up (S3,S3.1)
2-/1-Channel E-Stop (S4, S4.1)
Delay Time Seconds* (T1, T2)
0
9
1
2
*The amount of delay time between the opening of contacts 13-14, 23-24, 33-34 and 43-44, and
3
contacts 57-58, 67-68, 77-78, and 87-88.
6 5
4
Optional settings for Delay Time (T1/T2) rotary switches (in seconds):
Switch
Position
1
1
ES-TN-1H5
0
0
ES-TN-1H6
!
1
0
1
1
0
0
programmed OFF-delay timing function
to fail, due to circuit failure or power
loss, resulting in premature opening of
the delay contacts. The installation,
including its wiring, must be designed
to prevent any hazard which could
result from the loss of a programmed
output switching delay time.
DIP-Switch and Selector Switch Settings
Switch
Factory Setting
0 – Manual reset
0 – 1-Channel Monitoring
0 – Manual power-up
0 – 2-Channel E-stop
0 – 0 Seconds
0
1
2
3
4
0
0.5
1
2
4
0
5
10
20
30
WARNING . . .
Consequence of
OFF-Delay Failure
It is possible for any
Models ES-TN-14H5/-14H6
Optional Setting
1 – Auto reset
1 – 2-Channel Monitoring
1 – Auto power-up
1 – 1-Channel E-stop
See table below
5
6
7
8
9
6
8
10
15
20
50
70
100
150
200
WARNING . . .
!
After Switch Configuration
Follow the complete
checkout and
troubleshooting procedure (see page 12)
following any change in the settings to
the DIP switches or Time Delay Selector
Switches.
Seconds
Seconds