Danfoss ERC 112D VSC User Manual page 20

Electronic refrigeration controller for variable speed compressor
Table of Contents

Advertisement

User Guide | ERC 112D VSC Refrigeration Controller
"Euu"
EWU active on/OFF
Enable or disable early wake up.
Min. no
Max. yes
Default yes
"CLH"
Shop close hour
Shop is assumed to be closed when staying in ECO mode longer than shop close hour.
Min. 0 hour
Max. 24 hour
Default 6 hour
"ErL"
Early wake up time offset
Time of exiting ECO mode for next day=
Min. 0 min
Time of first activity to exit ECO mode - the early wake-up time.
Max. 240 min
"0": early wake up function disabled."
Default 120 min
"HoL"
Holiday Length
If controller stays for longer than HoL in ECO and no activity is detected, the controller will go into Holiday Mode. Early Wake Up
Min. 0 hour
is disabled.
Max. 999 hour
Default 72 hour
ECA
ECO management
"Eto"
Eco Temperature Offset
This parameter gives a relative temperature in degrees. It is the difference in temperature for ECO mode operation compared to
Min. -25,0 K
normal mode.
Max. 25.0 K
NOTE: setting a temperature offset may be illegal in some jurisdictions.
Default 4.0 K
"Hto"
Holiday Temperature Offset
Increase or decrease of temperature with respect to normal mode
Min. -25.0 K
during holiday mode.
Max. 25.0 K
Default 6.0 K
"diE"
ECO Differential
Thermostat differential for ECO.
Min. 0.0 K
Max. 10.0 K
Default 2.0 K
"FoE"
ECO Fan on cycle
On time for fan during compressor OFF period in ECO mode.
Min. 0 s
Max. 960 s
Default 0 s
"FSE"
ECO Fan stop cycle
OFF time for fan during compressor OFF period in ECO mode.
Min. 0 s
Max. 960 s
Default 0 s
"ELC"
ECO Cabinet light control
"on": always ON (Button is default to control light for all these options).
Default on
"oFF": always OFF.
"dor": door sensor only.
"ELd"
Eco Light Delay
This parameter causes a delay to the switch from normal to ECO mode
Min. 0 min
when the shop lights are switched ON or OFF. The ambient light sensor
Max. 10 min
detects the change in light level and causes a switch mode. With this
Default 5 min
parameter set to zero, the switch OFF mode occurs immediately.
If not set to zero (max: 10 minutes), then the change will be delayed by
the number of minutes set.
ASi
Assignments settings
"uSA"
MODBUS Safety
"no": MODBUS auto detection is enable and serial communication is available for configuration software tool.
Min. no
"yES": MODBUS communication is deactivated.
Max. yes
Default no
20 | BC286552322855en-000201