User Guide | ERC 112D VSC Refrigeration Controller
Introduction
Application
Advantages
Approvals
Password protected
2 | BC286552322855en-000201
Temperature control for refrigeration appliances.
Speed control of variable speed compressor.
Front panel mounting.
The latest generation CPU, plenty of memory
and high-end electronic components allow for
a uniquely versatile software. Three separate
password-protected user levels can be used to
control more than 300 different parameters to fit
all individual requirements.
R290/R600a end-use applications employing in
accordance to EN/IEC 60335-2-24, annex CC and
EN/IEC 60335-2-89, annex BB;
Glow wire according to EN/IEC 60335-1;
IEC/EN 60730
UL60730
NSF
CQC
EAC
Ukraine
The access level can be set separately for each
parameter using KoolProg Software Tool.
There are three levels of access 1, 2, 3:
- level 1 is for shop access;
- level 2 for technicians;
- level 3 for OEMs.
The access levels cannot be set using the buttons.
Passwords for the different levels can however be
altered for the level of access you have,
e.g. a level 2 user can change the password for
level 1 and level 2 but not level 3.
© Danfoss | DCS (vt) | 2019.07
Need help?
Do you have a question about the ERC 112D VSC and is the answer not in the manual?
Questions and answers
What does 4.5.6 connect to ?
Mostrador do controlar, fica travado , não mostra a temperatura real
The Danfoss ERC 112D VSC display may be stuck and not showing the actual temperature due to the "rLt" (Display Range Limit) parameter being set to restrict the displayed temperature to the cut-in / cut-out limits instead of the actual temperature. If "rLt" is set to "yes," it will not show the real temperature. To display the actual temperature, "rLt" must be set to "nO".
Additionally, the display might update slowly if a "ddL" (Display Delay) is set, causing a delay in showing temperature changes. Also, temperature updates can be blocked during fan OFF periods and only resume after the fan has been running for a while.
This answer is automatically generated
como entrar no parâmetro "rLt" (Limite da Faixa de Exibição) e fazer alteração?
To access and change the "rLt" (Display Range Limit) parameter on the Danfoss ERC 112D VSC, follow these steps:
1. Enter the parameter configuration mode.
2. Navigate through the parameter list to find "rLt".
3. Select "rLt" to view or change its value.
4. Set the value to “nO” to display the actual temperature or “yes” to restrict the display to cut-in/cut-out limits.
5. Confirm the selection to save the change.
The default setting is “nO”.